Carbon Monoxide Problems
from New Furnaces
| Several
case studies from the Iowa State University Extension show that carbon
monoxide hazards exist even with new gas appliances. Proper installation
and analysis are key to avoiding or solving these problems. |
|
While checking for CO in the outdoor air from a furnace
outlet (visible under the window in the far left of this photo), Dr. Saqib
Mukhtar was unable to approach any closer without exceeding maximum allowed
personal exposure concentrations. |
Carbon Monoxide (CO) can creep into living spaces and cause a variety
of health problems, sometimes even death. While old or poorly maintained
gas furnaces and other older appliances are often the sources of CO, new
heating appliances also cause CO problems. Many of these failures
arise from improper installation. As a housing engineer with Iowa State
University Extension, I encounter many CO-related problems.
What Can Go Wrong
I was once called to a home where the family dog was nearly blind, and
one of the occupants had experienced severe headaches and dizziness. The
furnace was a high-efficiency, direct-vent, sealed-combustion propane unit
with top mounted burners. In two years the furnace had filled with soot
and three of the five heat exchanger chambers had cracked above the top-mounted
burners, while all five of the large, open rivets holding the top of the
exchanger together had fallen out. This had allowed air to blow into the
flame chamber, which had disrupted the flame and forced it to the top of
the exchanger, causing the three cells to crack. The installation of this
new unit had other problems too, including too many bends in the discharge
and air intake pipes, and a reduction in pipe size from 3 inches to 2 inches.
Once the source of CO is located, it is important to discover how it
enters the house. In the above case, the furnace was producing extremely
high concentrations of CO, which was being vented outdoors below the windows
on the west side of the house. Concentrations of CO in the outdoor air
near the discharge vent exceeded 4,500 parts per million (ppm), the limit
of my combustion analyzer. Under certain weather and wind conditions, the
CO would find its way into the loose turn-of-the-century structure.
The owners of this house were dissatisfied with the service provided
by the original installer and contacted a different dealer. The second
dealer informed the owners that their new furnace had been recalled to
correct the rivet problem in the heat exchanger. Although there was a repair
kit for the rivets, the heat exchanger had to be replaced because it was
completely sooted up. The second dealer contacted the manufacturer, who
furnished a new heat exchanger. This dealer also corrected the venting
by installing larger vent pipes. In addition, the propane supplier replaced
the exterior gas regulator because of their concern over its operation.
Another case involved a new home with an induced-draft furnace on a
4-inch vent. The furnace installer had neglected to fasten and seal the
bottom plate of the furnace under the circulating blower. The furnace was
made for either a bottom return or a sidewall return, with bold, capitalized
warnings that the plate must be screwed down to prevent possible carbon
monoxide problems.
The family began having respiratory problems as soon as they moved into
their new home. A heating contractor installed an electronic air filter
and told them to operate the furnace blower continuously. But the return
was sucking air from the basement around the unfastened bottom plate. This
depressurized the basement to over 9 Pascals (Pa), causing a complete flow
reversal in the common furnace and water heater vent.
The family suffered from several respiratory and health problems, caused,
perhaps, by nitrogen dioxide from the water heater and dust off the basement
floor. Medical specialists did not attribute these problems to poor indoor
air quality, even after the family told them of the constant exposure for
more than two and a half years!
There were several other clues that the ductwork was defective. The
upstairs was difficult to heat and cool and, after the electronic air filter
was installed, the air conditioner coil had plugged with dirt in less than
one year. Why? Because dirty air from the basement floor was being drawn
directly into the furnace.
The heating contractor recommended increasing the house ventilation
rate by installing a new heat' recovery ventilator. However, the contractor
had not discovered the open bottom on the furnace, which I found during
pressure testing.
At another four-year old home, the owners complained that the pilot
on their water heater continually went out. The furnace was a direct-vent,
sealed-combustion furnace and the water heater was a natural-draft unit
with separate vent pipe. The heating contractor was unable to correct the
problem and told the homeowner the house was "too tight."
 |
| A secondary heat exchanger from a high efficiency
condensing furnace plugged with black soot. |
Further investigation revealed that the return ductwork
in the basement was extremely leaky. When the furnace blower operated,
the basement was depressurized to 8 Pa and the water heater backdrafted.
The owner noted that the vent pipe above the water heater would get ice
cold on chilly nights. After being shown what caused the problem, the heating
contractor air sealed the returns in the basement, added an extra upstairs
return, and opened the two basement supplies. After duct sealing, basement
depressurization was 3 Pa and the water heater vented adequately.
A fourth case concerned a homeowner who returned after a vacation to
find soot throughout his house. Almost on reflex, a contractor replaced
the furnace with a direct-vent, sealed-combustion unit, leaving the water
heater vented into the former common vent. The homeowner later complained
that the water heater sometimes spilled. He contacted numerous persons
who attempted to correct the problem. One of the contractors decided to
install a temperature-sensitive, anti-spill switch, which is designed to
shut off the water heater when hot gases spill from the draft diverter.
Unfortunately, during downdrafting, the incoming cold air diluted the hot
combustion gases and the spill switch never functioned. (These switches
are effective in shutting the units down when the vent is totally blocked,
and some manufacturers are now changing the name to "blocked vent switch.")
The real source of the problem was eventually found to be a 14-inch
roof-mounted attic fan. It operated automatically.(using a temperature
sensor) and would sometimes run for weeks at a time to reduce attic heat
in summer. When the fan operated, the basement was depressurized to 15
Pa (see "Drawbacks of Powered Attic Ventilators,"
HE
Nov/Dec '95, p. 5). This was an older one-and-a-half story house that
had many leaks connecting the basement to the attic. In addition, the homeowner
had recently put new steel siding on the house, and the installers had
blocked over the end gable vents and the soffit vents, replacing them with
much smaller and less effective venting.
Shutting off the fan in the attic decreased depressurization to 3 Pa.
While the problem was originally thought to lie with the old furnace, in
the end, simply shutting off this fan solved the problem.
Why Things Go Wrong
Two failures are basic to all combustion appliance CO problems: (1)
incomplete fuel combustion, and (2) a vent system that does not adequately
remove the exhaust. These two failures are often interrelated. For example,
during a flue reversal, all the products of combustion spill into the room
housing the appliance. The appliance then "breathes its own fumes." As
oxygen in the room is consumed, incomplete combustion occurs and CO is
produced.
Vent Failures
Combustion products usually go up the vent, but certain conditions may
cause them to spill at the draft diverter or out the burner ports. Buoyant
forces that cause combustion products to vent result from temperature differences.
The buoyant forces are small and easily overpowered by other, more powerful
forces. The buoyant (lifting) force, approximately 5 Pa, is only about
1/6 oz in a 4-inch-diameter round flue pipe. Wind forces, exhaust fans,
and the furnace blower are all more powerful and can reverse the flow in
the vents. Combustion appliances also compete for air. For example, when
a freplace and a furnace are both operating they both need outside air.
If the house is tight, they will compete with each other for the air they
need.
Technicians often hold a match near the draft hood to check for proper
draft, and this method is suggested in some manufacturers' literature.
However, holding a match is not a good way to check, because the match
is a hot source, and the smoke will tend to rise even if it is not being
pulled up into the draft hood. Instead, technicians should use a smoke
stick of neutral density, such as those used to check for infiltration
during house leakage tests.
 |
|
| Figure 1. The results of an overfiring test and the
resultant CO production from a furnace. The overfiring was measured by
clocking the meter (which gives input in Btu/h) and by measuring the gas
manifold pressure. The nominal firing rate was 105,000 Btu/h at 3.5 inches
gas manifold pressure. At this firing rate, CO production was under 20
ppm. As the gas manifold pressure was increased, the firing rate increased.
At 4.5 inches manifold pressure, CO production began to shoot up, and at
5.5 inches manifold pressure, the CO production was over 3,500 ppm and
the firing rate was 123,000 Btu/h. This is only a single example; different
burners will react differently. |
 |
| Looking into the exhaust end of a secondary heat exchanger,
Note the black soot and flaking rust where water from combustion has leaked
out. |
Vent failures are often sporadic, inter-mittent, and difficult to reproduce.
Because pressure differences are small, it takes only a small change to
cause warm gases to vent incorrectly. Often, a down-draft will occur when
the house is closed. Simply opening the front door once can change the
pressures, allowing warm air to go up the vent again. Auditors check-ing
for CO problems should always attempt to monitor venting under the worst
case scenario.
Overfiring
Overtiring, or overgassing, is another common source of CO. A properly
adjusted gas furnace or water heater produces hardly any CO. When too much
gas is supplied to the burner, suf-ficient oxygen does not flow into the
burner, and CO is produced.
I find overfiring to be a more common cause of CO problems in a home
than cracked heat ex-changers. Overfiring often occurs in conjunction with
intermittent vent failure and is therefore difficult to diagnose unless
proper procedures and equip-ment are used.
Overfired units typically still burn with a blue flame. Too often, without
proper test instruments, the heating contractor will assume that the unit
is burning clean. During sev-eral carbon monoxide conferences held here
in Iowa, we purposely over-fired furnaces and then asked heating contractors
to predict the potential for CO by using flame color. They were not able
to distinguish the problem until they were told and shown that the fur-nace
was misadjusted.
The differences between a properly adjusted furnace and an overtired
fur-nace are extreme. An overtired furnace can produce more than 4,500
ppm CO in the flue (see Figure 1). A simple reduction
of gas pressure, which takes two minutes to perform, can bring CO levels
back to below 20 ppm.
How do excess gas pressures occur? Some-times, the gas regulator can
fail, or, in some cases, the installing con-tractor does not per-form the
initial gas pressure adjustment. In yet other cases the heat-ing contractor
or home-owner, desiring more heat, may increase the gas flow by changing
the gas pressure adjustment. Overfiring may also be caused by improper
ori-fices, which can result when units are changed from propane to natural
gas or from natural gas to propane. The correct orifice is vital to proper
gas flow.
Manufacturers typically desire no overfiring beyond a tolerance of +2%.
Yet I find units 20%-30% overtired. Because overfiring cannot be diag-nosed
by flame color, it is vital that all contractors perform the following
steps:
-
Check the rate of gas flow to the burner, and check for overfiring by clocking
the meter (that is, use the test dial on the gas meter to verify that the
appliance is using the proper amount of gas).
-
Check manifold gas pressure using an accurate manometer.
-
Ensure that gas orifices are correct.
-
Measure carbon monoxide concen-trations in the combustion products. (Instruments
to measure CO in the flue products are readily available, and are vitally
necessary for carbon monoxide investigations. The same instrument can also
be used to mea-sure ambient air CO concentrations.)
Heat Exchanger Failures
The heat exchanger keeps the furnace exhaust from mixing with the house
air. Holes or cracks in the exchanger can cause serious problems. Holes
can allow the exhaust to enter the duct system and be distributed throughout
the house. Holes and cracks can also allow air from the blower to enter
the burner chamber and disrupt burner operation, increasing the amount
of CO produced. Air flow through large holes or cracks can cause combustion
product spillage from the burner ports--a very danger-ous situation. Condensing
furnaces also have a secondary heat exchanger, which removes heat from
the flue gases, caus-ing them to condense.
 |
| A small crack can mean big trouble,
especially when it is located on a heat exchanger as shown here. |
Some of the causes of premature heat exchanger failure are:
-
Incorrect temperature rise. The tempera-ture can be either too high
or too low--caused by incorrect blower speed selection, restricted ductwork,
insufficient ductwork, dirty filters, or lack of filters. The correct range
for temperature rise is on the infor-mation plate of each furnace.
-
Taking air from inside the house. Contaminants inside the house
are hard on high-efficiency units as they create acids in condensation,
which contributes to corrosion. Use sealed combustion and don't use contaminants
(such as aerosol sprays) in the house. A very common problem with older
units located near laundry machines has been corrosion due to chlorine
fumes.
-
Incorrect gasfiow rate. Many units are overtired, running rich and
hot. Overtired units do not have sufficient air for complete combustion.
Crack-ing of the heat exchanger, sooting, and CO can result from overfiring.
-
Oversizing. This causes rapid on/off cycling
without sufficient time to heat the furnace exchanger or the vent. Condensation
forms and does not get evaporated out. The "wet time" is excessive.
 |
| This new furnace has an open bottom section covered
with a plate, which the installers failed to attach properly. The unsecured
plate warped and allowed air to leak into the furnace from the basement,
instead of being pulled through the electronic air filter and return duct
on the right side of the furnace. |
Older "High Efficiency" Furnaces
Many of the first high-efficiency units installed in the 1980s were
poorly designed, and the metal in the exchangers was not adequate to stand
up to the condensing gases. These units have been failing. For instance,
in January 1996 I inspected an 86% efficient condensing furnace. The combustion
discharge at the base had rusted completely through. The burner was producing
several thousand ppm CO because air flow was insufficient. Unfortunately,
the combustion air fan pulled extra room air across the safety switch,
and the safety switch did not shut down the unit. The problem was found
by combustion gas analysis, and the furnace was replaced.
Preventing CO Poisoning
Carbon monoxide is produced when-ever a fuel does not burn completely.
CO poisoning will cause severe and permanent medical problems and death;
medical researchers report that 14%-40% of seriously poisoned patients
have delayed neurologic symptoms that may be disabling. CO is the leading
cause of poisoning deaths in the United States.
Too often people think that CO poisoning can-not happen to them, because
they live in a drafty older house or have a new furnace. This is not true.
As these cases reveal, CO poisoning can occur in older, loose houses or
newer, tight houses and can be caused by new fur-naces as well as old ones.
Carbon monoxide poisoning is pre-ventable. Annual maintenance of heat-ing
appliances by a qualified service technician and installation of reliable
detectors can reduce the needless costs, pain, and suffering CO poisoning
causes.
 |
| Here an induced draft furnace
and natural draft waterheater are vented into a common flue. While this
is a frequent configuration, it has potential hazards, including the possibility
of backdrafting from the waterheater's draft diverter. |
Thomas H. Greiner is an associate professor of agriculture and biosystems
engineering at Iowa State University Extension.