|
| Back to Contents Page |
Home
Energy Index |
About
Home
Energy |
| Home Energy Home Page
| Back Issues of Home Energy |
Home Energy Magazine Online March/April 1997
Sowing Conservation in Garden Apartments
by Steven McCarthy, Richard Taylor, and Bill
Van der Meer
Steven McCarthy, Richard Taylor, and Bill
Van der Meer are teachers at the Weatherization Training Center at the
Pennsylvania College of Technology.
Low-rise attached apartments pose different
challenges for energy auditors than either single-family or large multifamily
buildings. One project for a Pennsylvania housing authority shows some
of the situations auditors may find.
 |
| The photo above shows one of the 42 apartment buildings
within the 250-unit Penn Vale Housing Complex, where auditors performed
energy usage evaluation on ten different apartment types. Thirteen units
also received a comprehensive energy audit. |
Auditing low-rise garden apartments is different
from auditing single-family or high-rise multifamily buildings. While the
apartments don't have the complex patterns of air movement found in high
rises, they cannot simply be treated like single-family homes. Each unit
is affected by another unit; they share walls and sometimes attic space.
To treat each unit properly, auditors need to look at the construction
of the entire building.
The Lycoming County Housing Authority (LCHA)
pays the gas bills for tenants in its Penn Vale apartments. But if the
tenants use more than a preset reasonable amount of gas, they must pay
the difference to the authority. Last year, LCHA requested an analysis
and recalculation of its "reasonable usage" for different types of apartment,
along with an energy audit, from the Weatherization Training Center.
The Penn Vale subdivision consists of 250 apartments
in 42 buildings, composed primarily of one-, two-, and three-bedroom units
(plus four four-bedroom apartments). The apartments are all built on a
slab foundation and are clustered with four to six units per building.
All one-bedroom apartments are one story and are accessible to people with
disabilities. There are also one-story, two-bedroom accessible apartments.
The rest of the units have two stories.
All apartments have water heaters and forced-air
furnaces located in a mechanical room that is attached to the apartment
but is not accessible from inside. In the one-story apartments, most of
the ducts are located in the ventilated attic. In the two-story apartments,
ducts are located in the floor cavity between the first and second floor.
The complex was built in four phases, and there
is some variation among the buildings. Buildings erected during phase one
and two all have common, open attics above the apartments. Phase three
and four buildings have individual attics above each apartment. Sixty units
have instantaneous gas water heaters with added power vents, and 190 units
have power-vented, gas-fired storage water heaters.
The quality of construction at Penn Vale is very
good. All of the units inspected were well maintained. In general we found
no serious problems, but we did see some worthwhile opportunities for energy
savings.
| Table 1. Reasonable Expected Gas Use for Ten Types of
Apartment. |
| Unit Type |
Number of Units |
Expected Total Gas Use (Therms) |
Expected Total Gas Use (Dollars*) |
| One-bedroom inner units |
24 |
477 |
$206 |
| One-bedroom end units |
12 |
495 |
$317 |
| Two-bedroom inner units with separate attics |
97 |
587 |
$365 |
| Two-bedroom inner units with common attics |
39 |
514 |
$328 |
| Two-bedroom end accessible units |
2 |
613 |
$379 |
| Three-bedroom inner units |
4 |
642 |
$393 |
| Three-bedroom end units with separate attics |
48 |
748 |
$447 |
| Three-bedroom end units with common attics |
20 |
650 |
$398 |
| Four-bedroom inner units |
2 |
915 |
$527 |
| Four-bedroom end units |
2 |
946 |
$540 |
| Penn Vale total |
250 |
| *Gas costs are calculated based on utility charges: These
include a customer charge of $8.45 (which includes the first 7.9 ccf of
gas use), $0.5388/ccf for use up to 100 ccf, and $0.4115 for use over 100
ccf. |
Reasonable Expected Gas Usage
We determined expected gas usage for ten different
types of apartment in the complex (see Table 1).
To come up with reasonable numbers, we used historical gas usage for all
the apartments, weather data, and meter readings from six unoccupied units
during the month of March 1996. The unoccupied units had operating water
heaters and heat set at 72°F. The results were estimates of reasonable
usage by relatively energy-conscious tenants.
LCHA's previous estimates were not significantly
different from ours, although we did add a few categories. We divided the
two-bedroom inner and the three-bedroom end units into two categories when
we discovered that the units in buildings with a common attic space use
10% less gas than the units with individual separate attic spaces. These
two types of unit were built by different contractors in different years,
and they lose heat at different rates. The separate attics had more attic
vent area, which may cause cooler attic temperatures and more convection
losses through building cavities open to the attic.
As expected, the smallest (one-bedroom) units
use the least gas. The largest units use about 70% more gas than the smallest
units. Also as expected, the inner units use less gas (3% to 14%) than
the more-exposed end units.
The disabled-accessible units are the only single-story,
two-bedroom apartments in the complex. We expect that gas usage in these
units will vary greatly, depending on the nature of the tenant's disability.
Therefore we told LCHA that each of these units should be considered on
a case-by-case basis and paired with one of the other existing use categories
based on anticipated needs for heat, hot water, and cooking.
The Audit
We chose a varied cross-section of units and tested
for air leakage, did combustion analysis of the furnace, performed infrared
scanning, and checked the pressure balance. We also looked at heating and
baseload usage. During the inspection we took measurements and made observations
pertaining to safety, indoor air quality, and client behavior as it relates
to energy use.
Building Shell
We tested air leakage using a blower door. Apartment
air leakage rates ranged from 1,000 cubic feet per minute at 50 Pascals
(Pa) of house depressurization, or 1,000 CFM50, to 1,375 CFM50. This translated
to estimated natural air exchange rates from 0.6 to 0.8 air changes per
hour (ACH). While the blower door was running, we were able to feel air
leaking into the apartment around doors, windows, and baseboards, and at
electrical outlets. Air was also leaking from all supply and return registers
and from many attic access hatches.
Attic pressure testing indicated the existence
of some minor air leakage connections between the house and the attic.
These can most easily be treated from the attic. Except for the attic hatch
and the ductwork, we did not recommend any further air sealing from the
building interior.
We recommended that connections to the upper
attic be eliminated by duct and air sealing treatments. Due to the difficulty
and expense involved in gaining access to the small lower attics (above
the mechanical room and above the front entrance area), we proposed no
action for these areas.
 |
| Combustion analysis is performed on a 90%+ efficient
furnace inside the mechanical room of one unit. Note the register on the
supply plenum (covered with tape for testing), which provided heat to prevent
pipe freeze-ups. |
Pressure Testing
With the furnace blower operating, we took pressure
measurements to evaluate pressure imbalances both within the apartments
and between the apartments and the outdoors. We also checked the cumulative
effect of running all exhaust fans and the furnace fan together, and tested
the flow on all exhaust fans.
Whenever furnace fans were operating, we found
the apartments to be depressurized, suggesting supply duct leakage to the
outside. The average amount of depressurization was about 5 Pa, and in
the two worst cases, it was as high as 8 Pa.
When the bedroom or bathroom doors were closed
and the furnace fan was operating, the depressurization in the rest of
the unit increased to about 7 Pa average, and in the worst apartment to
10 Pa. At the same time, the closed rooms were pressurized from 1 to 6
Pa, with the average room pressure being about 3 Pa.
The pressure imbalances that occurred whenever
the furnace fans operated were causing increased air leakage above what
we found in our blower door tests. Cold outside air is pulled into any
area of the apartment that is depressurized and warm heated air is pushed
out of spaces that are pressurized. This increase in the air leakage rate
results in higher heating costs. The major cause of the pressure imbalances
in these apartments is duct leakage.
Duct Leakage
Since the ducts run in the cavity between the
first and second floors of two-story units, supply registers are located
in the first-story ceiling to serve the downstairs, and in the second-story
floor to serve the upstairs.
We found from pressure pan testing that the warm
air distribution systems leak significantly to the outside. While there
are many small leakage sites, the most significant "leak" was a supply
register in each apartment's vented mechanical room.
The mechanical room is ventilated by required
combustion air vents in the exterior door. However, the room is heated
to keep pipes from freezing. Pipe freezing problems are common in vented
mechanical rooms throughout North America, and the American Gas Association
has recognized the problem.
Battelle Pacific Northwest National Laboratory
has recently researched the issue of combustion air openings and pipe freezing.
This research will be the basis for a modification of the next revision
of the National Fuel Gas Code (NFPA 54), and we used it to form our recommendations
for duct treatment.
A long-term solution for Penn Vale would be to
replace existing furnaces and water heaters with sealed-combustion units.
Sealed-combustion appliances draw air for combustion directly from the
outside, so the vents on the door to the mechanical room could be sealed
off completely.
In the short term, we made the following recommendations:
-
Insulate all water piping in the mechanical room,
including cold water supply pipes. Also verify that all elbows are insulated.
-
Remove the supply plenum register and seal the opening.
-
Install a reducer plate on existing furnace room
door vents, modifying the combustion air openings to fulfill the requirements
in the proposed National Fuel Gas Code.
We also recommended treatment of accessible sections
of the distribution system. We suggested eliminating and sealing all filter
slots that have been cut into the ducts, and installing the filter on the
return grill or in the furnace cabinet instead.
Occupant Survey and Behavior Observations
We informally asked residents in occupied apartments
about energy bills, temperatures in the apartment, comfort, thermostat
setting and use, and exhaust fan use.
Half of the occupied apartments we inspected
or tested were being heated to between 75°F and 80°F. Recording
thermometers placed in unoccupied apartments showed a temperature difference
of 4°F between the first and second floor, with the upstairs always
being overheated.
Occupants always said that the upstairs was the
warmest part of the apartment, and some said it was uncomfortably hot.
A surprising number of second floor windows were open on days when the
outside temperature was between 40°F and 45°F.
Temperature stratification on the first floor,
which is to some extent more extreme due to the placement of the supply
registers in the ceiling, causes occupants to compensate with higher thermostat
settings. (For example, to get a 72°F temperature while sitting in
a chair on the first floor may require setting the thermostat to 75°F,
which in turn will heat the upstairs to 78°F.)
In unoccupied units, when all upstairs bedroom
registers were closed, there was no measurable temperature difference between
the first and second floor. So we recommended closing or blocking off all
second floor bedroom registers to deliver more heat downstairs and achieve
better heat rise temperatures. (Note that it's very important to ensure
sufficient air flow through the remaining ducts.) Since the ducts are located
in conditioned space (between floors), any increased duct leakage caused
by closing registers should be to the inside.
Many occupants adjusted their thermostat continuously,
sometimes setting it at 60°F when they were hot and adjusting it up
to 80°F when they were cold. We recommended installing new thermostats
that limit room temperature to 75°F maximum in any apartment that exceeds
the reasonable usage. We also suggested installing inexpensive stick-on
thermometers next to the thermostat in all apartments, with the 70°F
point marked as "best room temperature."
The occupants should be educated concerning temperature
setpoint and comfort, temperature setting and energy consumption, thermostat
use, and exhaust fan use.
 |
| Combustion air inlets in the door to the mechanical
room. The existence of these intentional openings and a supply duct on
the furnace plenum combined to produce significant house depressurization
during the blower cycle. |
Building Thermal Flaws
We used infrared scanning to assess the performance
and completeness of wall and ceiling insulation. We did the infrared scan
while depressurizing the building with the blower door, in order to locate
air leakage pathways within the building shell.
We found some evidence of poorly installed or
missing insulation, and of air flow through the building framework, especially
in second-floor sloped ceilings. However, we didn't recommend any treatment,
because insulation repair in this area would be too difficult and expensive
to be cost-effective.
Attics were already insulated with 12 to 13 inches
of loose fill fiberglass or R-30 rated fiberglass batts. Loose-fill insulation
was somewhat compressed around the attic hatch and along walkways. Only
two attic hatches were insulated. No moisture problems were visible in
the attic. All attics were ventilated.
Open wiring penetrations in the top plate were
leaking air. This problem was most severe above the wall that separates
the bathroom from the adjacent bedroom. This wall also contains a plumbing
stack that was leaking a significant amount of air.
 |
| Pressure pan testing revealed significant leakage
to the outside. Since the ducts were contained within the building envelope,
most of the leakage was attributed to a register supplying heated air to
the mechanical room. |
Appliances
The temperature of the hot water at kitchen faucets
ranged from 105°F to 149°F. Considering the capacity of the water
tank and that the apartments do not have dishwashers, maintaining the water
temperature above 120°F is unnecessary.
We measured furnace flue gas with a combustion
analyzer to determine oxygen and carbon monoxide (CO) content and to assess
the integrity of the heat exchanger. Fan on/off temperatures and heat rise
were measured with a digital thermometer. Finally, we checked the thermostat
heat anticipator setting. (The heat anticipator fools the thermostat into
turning off the gas early. This lets the space coast up to the desired
temperature from residual heat in the furnace.)
Furnace testing did not reveal any problems in
need of immediate attention. We did suggest verifying the gas manifold
pressure on all furnaces to be 3.5 inches of water column and adjusting
it if necessary; changing all air filters two times during the heating
season; and setting all thermostat anticipators to 0.15 amps, an appropriate
setting for these furnaces.
We tested the gas range for burner operation
and CO production, and the gas line for gas leaks. All accessible gas lines
in the mechanical room were checked for leaks.
Most ranges and ovens were found to be in good
operating condition. Carbon monoxide testing showed that CO concentrations
at start-up varied from 115 to 200 parts per million (ppm). After a period
of warm-up, they dropped to less than 50 ppm. One stovetop burner out of
12 stoves would not light, and we found one gas leak between the flexible
connector and the gas piping.
We recommended using a combustible gas leak detector
or a leak detection solution each time gas piping is changed or modified
or whenever the gas cock is closed and opened.
 |
| Even though the main emphasis of this study was on
gas consumption, auditors also monitored refrigerator electrical consumption
and temperatures using a digital thermometer and a watt meter. Most of
the refrigerators were deemed to be operating fairly efficiently, although
auditors recommended that one guzzler be replaced. |
The Housing Authority's Response
LCHA has chosen one building as a pilot and has
begun implementing several of the suggestions we made. These are the actions
they've taken so far:
-
Thermostat anticipators checked and reset.
-
Second-floor bedroom supply registers sealed closed.
-
Mechanical room combustion air grille reduced by
50%.
-
Supply register in the mechanical room replaced
with a dampered 3-inch duct to the pipe area.
-
Attic hatch weatherstripped and insulated with 3
inches of extruded polystyrene board.
-
Plumbing stack caulked.
In addition, they have checked for gas leaks in
all units, and set all water heaters to 120°F.
Lessons Learned
Garden apartments are unlike high-rises because
the units should be audited individually. However, one doesn't need to
audit every apartment in a complex. Most of the problems we identified
at Penn Vale were common to all apartments of the same construction type.
By identifying the various categories of apartment--by number of stories,
number of bedrooms, location, phase of construction, energy bills, and
short-term monitoring results--we were able to choose a cross-section of
apartment types to inspect. The inspection turned up some significant recurring
problems in all the units, such as the supply register in the mechanical
room, and temperature stratification in the two-story apartments. We were
then able to make recommendations for all the units in the complex.
| Back to Contents Page |
Home
Energy Index |
About
Home
Energy |
| Home Energy Home Page
| Back Issues of Home Energy |
Home Energy can be reached at: contact@homeenergy.org
Home Energy magazine -- Please read our Copyright
Notice
|