|
The Best Boiler
and
Water Heating
Retrofits
by Mary Sue Lobenstein
and Martha J. Hewett
| Over the past decade, measures
for improving the efficiency of steam and hydronic boilers and water heating
systems in multifamily buildings have been tried and intensively monitored.
Based on this experience, here is our assessment of what works for retrofitting
these systems. |
When the Minneapolis
Energy Office (now the Center for Energy and Environment) first addressed
the issue of improving energy efficiency in multifamily buildings in 1981,
the task was a little daunting. For one thing, there was no documented
research on multifamily retrofits, making it difficult to identify recommendations,
quantify savings, and recognize the specific conditions under which savings
could be expected. Most information was in the form of case studies published
by manufacturers in sales literature.
We also found considerable suspicion among multifamily
building owners about energy retrofits. They had pretty much heard it all:
every new device or piece of equipment on the market was an amazing breakthrough,
"guaranteed to reduce energy bills by 25% with a one-year payback."
Property owners lacked the technical expertise to distinguish truly cost-effective
retrofits from snake oil. An additional challenge was the fact that multifamily
building owners tend to avoid long-term investments.
Since then, we and other groups have systematically
fieldtested a wide range of energy conservation measures for boilers and
domestic water heaters in low-rise multifamily buildings. We avoided "way-out"
retrofits, and concentrated on measuring the actual performance of widely
recommended measures. This fieldwork has provided independent and objective
test data that building owners can trust. This article presents a quick
review of what we have learned over the years.
Finding the
Best Measures
In our research, we focused on the Minneapolis-St.
Paul area, where the vast majority of multifamily buildings are two- to
seven-story walk-ups (no elevators) of 6 to 60 units. We identified two
major groups of multifamily buildings: steam-heated buildings built between
the turn of the century and World War II, and hydronic-heated buildings
built since World War II (see "Minneapolis-St.
Paul Building Types").
In all buildings, research emphasized mechanical
system retrofits, since most envelope measures had already been implemented,
were physically impossible to implement, or exceeded owners' payback criteria
(typically one to three years). Research methods ranged from simple analysis
of pre- and post-retrofit billing data to long-term intensive monitoring.
Heading Up
Steam Retrofits
Research in steam buildings has covered four
main retrofit options (see Table 1):
Correcting uneven heating
Tune-ups of older coal-to-gas conversion boilers.
Installing vent dampers.
Converting buildings from steam to hot water heat.
We did not study boiler replacements because
the options for high-efficiency steam boiler replacements are limited.
(Some condensing steam boilers are available now, but most of them are
designed for industrial applications.) We also wanted to focus on the most
cost-effective measures that owners can afford without rebates or other
assistance.
|
Table 1. Performance
of Retrofits for Central Steam Heating Systems
|
|
|
|
|
|
|
| Measure |
Average
Energy
Savings |
Average
Percent
Savings1 |
Range
of
Savings |
Average
Cost
|
Average
Payback
(Range) |
Sample
Size |
| Improved boiler control and main line and
radiator air venting, single-pipe steam |
1,800 therms |
10% |
-14%-25% |
$1,100 |
1.3 years median
(0.4 to infinite) |
13 |
| Tune-up of atmospheric coal-to-gas conversion
boiler |
not
available |
4%
heating
gas use |
3%-5% |
$160 |
0.4 years (0.3-0.5) |
4 |
| Tune-up of atmospheric coal-to-gas conversion
boiler |
710 therms |
6%
heating
gas use |
0%-14% |
$160 |
0.51 years median
(0.2 to infinite) |
6 |
| Vent dampers on atmospheric brickset coal-to-gas
conversion boiler and tank-type water heater(s) |
770 therms |
6% |
1%-12% |
$2,400 |
20 years (3.2-36.9) |
2 |
Vent dampers on atmospheric brickset coal-to-
gas conversion boiler only |
1,400 therms |
9% |
6%-12% |
$1,300 |
2 years
(1.2-3.5) |
4 |
| Two-pipe steam-to-hot water conversion |
3,900 therms |
27% |
16%-39% |
$28,0001 |
12 years (5.5-27.3) |
11 |
| Single pipe steam to hot water conversion |
4,400 therms |
19% |
13%-27% |
$58,000 |
34 years (19.1-51.3) |
4 |
| 1Savings are given as percentage
of whole-building gas use, except where noted. |
|
|
|
|
|
|
Uneven Heating: An Open Window
of Opportunity
The worst source of inefficiency we found in
steam buildings was uneven heating. To minimize complaints from residents
in cooler areas, building owners grossly overheat other areas, leading
tenants to open their windows for relief. (In fact, many older contractors
have told us that in the original design of steam systems, the idea was
to overheat the building and let individual tenants regulate their heat
by opening and closing their windows!)
We intensively monitored boiler cycles and the
movement of steam through the distribution system at a prototypical test
building. Through this we learned that the primary causes of uneven heating
were large differences in steam arrival times combined with short boiler
cycles (see "The Art and Science of Balancing Single-Pipe
Steam Systems," EA&R Mar/Apr '87, p. 24).
We developed a strategy for balancing steam distribution
that involved installing a thermostat with an adjustable dead band, and
adding very high capacity (orifice of 5/16-in) main-line
air vents, as well as larger radiator air vents in some locations. This
steam balancing reduced total building gas use by an average of 10% with
a median payback of 1.3 years in 13 pilot buildings. Extensive work on
steam balancing in Chicago has shown similar results.
Tune-Ups for the Converted
Many of these older steam buildings have boilers
that have been converted from coal to natural gas, making them good candidates
for tune-ups for several reasons. First, the flue gas passages were grossly
oversized for gas, resulting in significant excess air and poor heat transfer.
Second, local codes offered flexibility in modifying conversion boilers.
And third, maintenance on most of this equipment had been deferred.
Techniques used to reduce excess air and stack
temperature included adjusting the fixed or motorized draft louvers, installing
flue restrictors, installing baffles on the bridge walls of brickset boilers,
sealing uncontrolled secondary air leaks into the combustion chamber, and
adjusting the firing rate. (Turbulators are a common retrofit that we did
not install except as a last resort. We found that the other measures cost
less and often work better than turbulators to reduce stack temperature.)
Savings for tune-ups ranged from 0% to 14% of space heating use, with typical
paybacks of about six months.
While tune-ups sound trivially simple, they require
a well-trained pool of contractors with access to electronic equipment,
and we found that we had to identify and teach this pool ourselves (see
"Boiler Tune-Up: Improving the `MPG' of Multifamily Buildings,"
HE Sept/Oct '89, p. 21).
Putting a Damper on Heat Loss
The large thermal mass and vent size of coal-to-gas
conversion boilers, combined with the massive masonry chimneys common in
multifamily buildings, suggest large off-cycle losses and significant potential
for vent dampers (see "Do Vent Dampers Work in Multifamily Buildings?"
HE Mar/Apr '90, p. 27). We also expected the presence of barometric
dampers for draft relief to make vent dampers more effective in conversion
boilers, since the barometric damper swings shut when the vent damper closes,
reducing air flow through the boiler and retaining heat.
The brickset boilers we tested showed average
savings of 8.6% of total building gas use, with an average payback of 2.2
years. Oddly, when vent dampers were added to the water heaters as well,
one of our test buildings showed greater savings while another showed almost
no savings, a result we were unable to explain.
Getting into Hot Water
The final area we investigated for steam buildings
was conversion to hot water heat, which produced savings averaging 18%
of total gas use for single-pipe steam (SPS) buildings and 27% for two-pipe
steam (TPS) buildings. The SPS conversions required new supply and return
lines and new radiation, and costs averaged $58,000 ($3/ft2). Comparatively,
TPS conversions reused the existing piping and radiators (with minor modifications),
and costs averaged $28,000 ($1.50/ft2). While the median payback for this
retrofit is long (10 years), conversion from steam to hot-water distribution
provides compelling advantages: improved tenant comfort and system reliability,
increased building resale value, and lower maintenance costs (for example,
hydronic systems do not require regular water treatment, blowdown, or trap
maintenance).
Hot Retrofits
for Hydronics
Research in buildings heated with hot water has
covered five main options (see Table 2):
- Resets and cutouts.
- Vent dampers.
- Tune-ups of gas-designed boilers.
- Energy cost allocation systems.
- Front-end modular boilers.
Resets and Cutouts
In early energy audits, we found many hydronic
buildings operating with constant boiler water temperature or with manual
resetting only. As a result, one of the first measures we tested was a
reset control that varied boiler water temperature between 110deg.F and
185deg.F as a function of outdoor temperature, combined with a cutout control
that shut the boiler off on warm days. (Although manufacturers of cast-iron
boilers suggest that their equipment should not operate below 140deg.F,
common practice in Minneapolis and Saint Paul is to reset temperatures
as low as 110deg.F. We have put resets on them for the past ten years and
have never had a problem, and contractors have been doing it for 30 years
or more.)
Tests of resets and cutouts on cast-iron boilers
showed savings of 18% of space heating use with an average payback of 1.2
years (see "Outdoor Resets and Cutouts: Quick Fixes for
Hot Water Heating," HE Nov/Dec '88, p.15). Before-and-after
tests of automatic versus manual reset, both with automatic cutouts, showed
savings of 10% of total gas use (about 14% of space heating use) with paybacks
of less than one year.
These results were confirmed in a later pilot
project, which achieved savings of 9% of total gas use (about 13% of space
heating use) in eight buildings. A Wisconsin study found somewhat less
savings (7% of space heating use) for a group of six four- to nine-unit
buildings, but in most of these cases water did not circulate through the
main distribution system unless at least one zone was calling for heat,
whereas the larger buildings studied in Minnesota all had constant circulation.
On steel fire tube boilers, resetting the boiler
water temperature directly carries greater risks of thermal shock and corrosion.
In these buildings, we tested resetting of the distribution water using
a three-way mixing valve, which is more expensive due to both the piping
involved and the need for a modulating control. Savings averaged only 9.5%
of space heating gas use, lower than for direct resetting of boiler water,
and paybacks were considerably longer.
Part of the difference in performance for resets
on steel fire tube boilers results from the fact that resetting the distribution
water temperature does not improve the seasonal efficiency of the boiler,
but resetting the boiler water temperature does. Based on direct input-output
measurements CEE has done with cast-iron gas-designed boilers, we would
expect seasonal efficiency to improve by 1.5%-3% in going from constant
temperature control to reset control.
An alternative strategy to using a mixing valve
for steel fire tube boiler applications is to use a reset that has the
capability of setting a minimum boiler water temperature. Savings for this
have not been measured to date but would be expected to be lower, since
resetting of boiler water temperatures takes place in a narrower range
(for instance, 140deg.F-185deg.F).
|
Table 2.
Performance of Retrofits for Central Hydronic Heating Systems
|
|
|
|
|
|
|
| Measure |
Average
Energy
Savings |
Average
Percent
Savings1 |
Range
of
Savings |
Average
Cost
|
Average
Payback
(Range) |
Sample
Size |
| Boiler water reset and cutout control versus
constant temp and manual shutoff, ATM CI boiler |
1,100 therms |
18%
heating
gas use |
10%-25% |
$450 |
1.2 years
(0.3-2.8) |
4 |
| Boiler water reset versus manual reset, ATM
CI boiler |
1,100 therms |
10% |
4%-16% |
$250 |
0.5 years (0.2-1.0) |
5 |
| Boiler water reset and cutout control versus
various preconditions, ATM CI boiler |
1,200therms |
9% |
5%-18% |
$630 |
5.1 years
(0.2-24.3) |
8 |
| Distribution water reset versus constant temp,
power SFT boiler |
2,100 therms |
9.5%
heating
gas use |
5%-13% |
$4,000 |
4.8years (2.3-8.1) |
3 |
| Electronic ignition and vent dampers on gas-designed
CI ATM boiler(s) and tank-type water heater(s) |
780 therms |
6.5% |
-1.5%-9% |
$2,300 |
4.4 years median
(4.0 to infinite) |
4 |
| Electronic ignition and vent dampers on gas-designed
CI ATM boiler(s) only |
210 therms |
2% |
1.6%-2.1% |
$1,400 |
14.4 years (8.2-20.7) |
2 |
| Tune-up of coal to gas conversion boilers
|
220 therms |
2% |
1%-3% |
$160
2.0 years |
(1.1-4.1) |
4
(1 PWR,
3 ATM) |
| Tune-up of gas-designed CI ATM
boiler |
78 therms |
1%
heating
gas use |
0.4%-3.0% |
$120 |
(.09-infinate) |
3 |
| Energy cost allocation |
1,500 therms |
16% |
9%-22% |
$1,300 |
1.4 years
(0.6-2.7) |
9 |
| Front end modular boiler |
4,800 therms |
8% |
-3.7%-19% |
$35,000 |
21 years median
(6.7-infinite) |
8 |
| 1Savings are given as percentage
of whole-building gas use, except where noted. |
|
|
|
|
|
|
| Abbreviations: |
ATM |
atmospheric boiler |
CI |
cast-iron |
|
|
|
PWR |
power (forced-draft) burner |
SFT |
steel fire tube |
|
|
Installing Vent Dampers
We anticipated lower savings from vent dampers
in newer hydronically heated buildings because of the lower thermal mass
of the boilers and because draft relief is provided by draft hoods. This
allows air to flow continuously through the boiler (picking up heat and
spilling it out the draft hood) when the vent damper closes. In addition,
the vent dampers were tested on buildings that already had resets, and
thus lower off-cycle losses.
Savings averaged 6.5% of total gas use with both
boiler and water heater dampers active, but only 1.9% with only the boiler
dampers active. These results are consistent with those from tests in single-family
homes done by the Institute of Gas Technology in 1976 and 1980, which showed
vent dampers on the water heater to be critical to overall savings.
To maximize the savings, we installed quick-closing,
tight-fitting vent dampers and electronic ignitions, which inflated the
cost considerably over a more typical retrofit with thermal dampers on
the water heaters and slower dampers on the boilers.
Tune-Ups Get
Thumbs-Down
Tune-ups of gas-designed boilers were limited
by code restrictions on the installation of flue restrictors and on adjustments
to input, as well as by the fact that the secondary air openings were fixed.
Tune-ups by both CEE and a Wisconsin group showed essentially no savings.
Allocating Energy Costs
A more novel retrofit strategy tested on hydronic
buildings was the use of energy cost allocation systems to apportion gas
costs among individual apartments on the basis of use. We studied nine
buildings that had run-time meters installed to measure the length of time
that zone valves were open. Savings of 16% of total gas use were observed,
simply from making residents directly responsible for energy costs, with
a payback of 1.4 years. These results agree with a 1983 study by Lou McClelland
at the University of Colorado at Boulder, which compared 83 properties
before and after tenant payment was introduced and found average energy
savings of 10%-20%. Similar data is also available from Europe, where energy
cost allocation is widespread.
Adding Front-End Boilers
The final heating system measure tested in newer
hydronic buildings was to supplement existing boiler systems with small
"front-end" boilers that could heat the buildings more efficiently
under low load conditions (see "Front-End Modular Boilers:
Lessons from the Real World," HE Mar/Apr '91, p. 19). For
two systems installed by CEE and six installed by a contractor and monitored
by CEE, savings ranged from -3.7% to 18.5% of total building energy use
and averaged 7.7%. These savings were much lower than expected.
Somewhat better results were achieved by the
Energy and Environmental Resource Center for four installations that were
more closely monitored and precisely operated than the CEE cases, since
they were part of a shared-savings program. Savings for these cases ranged
from 6.8% to 18.3% of total building energy use and averaged 13.3%.
The best candidates for this retrofit appear
to be existing boilers that have low seasonal efficiencies (such as atmospheric
boilers) and are grossly oversized for the building load. Using the front-end
boiler to provide domestic hot water also increases savings potential.
In spite of the lower-than-expected savings and
the fact that front-end systems were relatively complicated to install
and operate, other benefits might make front-end boilers attractive to
an owner. These include availability of backup and the ability to forestall
replacing an aging, existing boiler.
Hot and Cold
Running Retrofits
Domestic hot-water research has focused on two
main areas (see Table 3):
- Cost-effective options at the time of construction or equipment replacement.
- Controls for systems with constant recirculation loops.
New Water
Heater Options
In order to identify the most cost-effective
equipment options at the time of construction or replacement, CEE tested
two types of higher-efficiency water heater against standard tank-type
heaters. The first was a tank-type heater with an integral flue damper
upstream of the draft diverter. Savings from installing this type of heater
were small enough that paybacks were over 10 years, in spite of its modest
incremental cost of $560. This is a somewhat moot point, since most commercial
tank-type heaters manufactured after January 1994 must have integral flue
dampers in order to meet new efficiency standards. However, these results
are still worth noting, since local supplies of tank-type heaters without
integral dampers may still dominate actual sales.
The second type of high-efficiency heater tested
was a power-vented condensing unit. It produced dramatic savings of 28%
of service water heating energy use, but at such a high incremental cost
($2,400) that paybacks were close to 20 years.
Temperature Controls
The only true retrofit measure tested was the
strategy of resetting the tank and recirculation loop temperature from
about 145deg.F to 110deg.F in buildings with constant recirculation of
domestic hot water (see "Controlling Recirculation Loop
Heat Losses," HE Jan/Feb '93, p. 9). Two controls were
tested--one that resets based on the time of day and one that resets based
on actual demand on the service hot water heater.
The time-based control saved about 10% but had
more operation and maintenance problems. The demand-based control reduced
water heating energy use by 16% and had fewer operational problems; as
a result, it is recommended over the time-based control. Both controls
had an average payback of about two years.
|
Minneapolis-St. Paul
Building Types
Two types of multifamily building are predominant
in Minneapolis and St. Paul. Within each type there is a considerable degree
of consistency in envelope and mechanical system characteristics, but the
one is much different from the other. The first type includes buildings
constructed between the turn of the century and World War II. The second
type includes buildings constructed since World War II.
Pre-World War II
The buildings built prior to World War II have
accessible attic cavities under flat roofs, which typically contain at
least 6 or 8 in of insulation. These buildings have masonry walls, making
it impossible to blow in wall insulation. Exterior wall insulation is prohibitively
expensive. Housing maintenance codes have made storm windows mandatory
for years.
The worst infiltration problems in these older
buildings stem from grossly uneven heating, which leads people to open
windows even in the coldest weather, a problem impossible to solve with
typical air sealing techniques. Nearly all of these buildings have steam
heating systems, and these are almost always controlled as a single zone.
Most of the distribution systems are of single-pipe design, with steam
and condensate flowing in opposite directions through the same mains and
risers, although we found two-pipe systems in buildings dating from the
1920s and 1930s. The systems typically operate at less than 1 pound per
square inch gauge (psig). (In other places, like New York, typical operating
pressures may be as high as 5 psig for similar systems; but, these pressures
can be reduced to less then 1 psig through balancing.) Most buildings have
massive site-built steel fire tube or cast-iron boilers, which have been
converted from coal to natural gas and have atmospheric burners, frequently
with modulating secondary air louvers.
Post-World War II
The buildings constructed since World War II
typically have only a 10-in to 12-in joist cavity available for roof insulation,
with 4 to 8 in of insulation already installed. The walls are wood framed
with brick or stucco veneers, but typically have 3 in of insulation. These
buildings have multizone hydronic heating systems with individual control
of space temperature in each apartment. Many are heated by low-mass, gas-fired,
cast-iron packaged boilers, though some of the larger buildings have packaged
gas or oil power burner boilers of steel fire tube construction.
The most common domestic water heating system
in buildings of both eras is a single commercial tank-type water heater
or a pair of heaters plumbed in parallel. Some buildings use the space
heating boiler to heat domestic hot water, which is stored in an insulated
tank. Only the larger buildings (40 units or more) recirculate service
water with a pump; the smaller buildings, which make up the majority of
the stock, have no recirculation.
Energy Usage Patterns
Total gas use in a typical Minneapolis multifamily
building averages about 80,000 Btu/ft2/yr, with steam-heated buildings
significantly higher than hot-water-heated buildings (86,300 Btu/ft2/yr
versus 70,200 Btu/ft2/yr). Not surprisingly, space heating accounts for
the largest portion of this total consumption, or about 72% on average.
For a typical building, this translates into about 12,095 therms annually.
The second most important gas end use is domestic hot water, which accounts
for 21% of total use, or about 3,530 therms annually in a prototypical
building. Gas cooking stoves and dryers generally account for 6% and 1%
of end use respectively (1,005 therms and 170 therms annually).
|
The Key to
Program Success
Confirmed energy savings ensure credibility and
retrofit performance, but they are only half of the formula. The other
half is setting up a comprehensive implementation program to ensure that
the appropriate retrofits are actually installed and that they are installed
correctly.
The first step involves working actively with
trade allies, such as suppliers and contractors, to introduce new technologies
into the marketplace and promote them. Our experience has also shown that
contractors need assistance and training in the technical aspects of completing
retrofits properly, both for unusual or innovative technologies (such as
steam to hot water conversion and front-end modular boilers) and for ones
that have been around for a while (such as boiler tune-ups, resets, and
modular boiler installations).
Multifamily building owners also need a convenient,
one-stop service that not only identifies the appropriate retrofits, but
makes the installation of those retrofits as easy for them as possible.
This means specifying particular equipment, using prescreened and trained
contractors, and making postinstallation inspections to ensure quality.
In addition, to minimize confusion about the installed retrofits on the
part of building caretakers and maintenance staff, we developed simple
operating instructions and guidelines for efficient operation, which are
laminated and posted in the boiler room.
An effective program should also include financial
incentives, such as rebates or low-interest loans, to ensure a high rate
of installation in a market that is driven largely by first costs. However,
we have found that financial incentives need not always be large. Throughout
the 1980s, using this one-stop approach and only limited utility rebates,
we audited over 1,500 buildings, 40% of which implemented measures through
our program and an additional 30% of which implemented the measures using
our information and their own contractors.
For some retrofits, our extensive work with multifamily
owners has so transformed the market in the Twin Cities that it is difficult
today to find buildings in which these measures have not been implemented.
For instance, since 1990 we have audited about 1,200 additional buildings,
but the implementation rate has dropped to about 30% as a result of this
market saturation.
What's Next?
For central boilers with inputs larger than 300,000
Btu/h, one of the big unresolved technical issues concerns quantifying
seasonal efficiency. Unfortunately there is currently no standardized test
procedure for determining the seasonal efficiency of commercial boilers
of this size, and most manufacturers only give steady-state thermal efficiency,
which is a poor predictor of annual performance.
ASHRAE has recently set up a standards committee,
headed by CEE staff, which is working on developing a standardized test
procedure to determine annual fuel efficiency. Once completed, it will
be of enormous benefit in helping practitioners to determine the cost-effectiveness
of various boiler replacement options and to pin down more precisely case-by-case
savings estimates for boiler retrofits such as resets and vent dampers.
For new construction in the multifamily sector,
one issue that needs to be addressed is the trend toward increased use
of electric heat--a trend driven mostly by first costs and by the desire
to have tenants pay their own heat. (As discussed above, electric heat
is not the only way to have tenants pay for what they use; energy cost
allocation systems can apportion fuel use among tenants.) According to
the U.S. Energy Information Administration, in 1975 19% of the multifamily
housing stock nationwide was heated with electricity, but by 1990 this
figure had risen to 34%. As this new housing stock ages, this will become
a retrofit issue, especially since the majority of multifamily buildings
house low-income people.
Finally, as utility funding for demand-side management
programs declines in the coming years, rebates and incentives are also
expected to decline. This trend will make it necessary to come up with
alternate financing scenarios that still provide building owners with a
positive cash flow and low up-front costs. One option that has been tried
in some commercial markets is tying loans for cost-effective retrofits
to the building meter or account, rather than to a specific customer. This
strategy encourages an owner to install retrofits that are beneficial in
the long run even if that particular owner sells the building. Each new
owner becomes responsible for taking over the repayment of the loan as
the building changes hands. Since the new owner is presumably reaping the
benefits of the retrofit, the strategy is fair to all players.
|
Table 3 Performance
of Retrofits for Central Domestic Hot Water
|
|
|
|
|
|
|
| Measure |
Average
Energy
Savings |
Average
Percent
Savings1 |
Range
of
Savings |
Average
Cost
|
Average
Payback
(Range) |
Sample
Size |
| Water heater with integral flue damper versus
standard tank-type water heater |
110 therms |
5% |
(4.1%-
6.1%) |
$560
(incremental) |
10.6 years
(9.0-12.2) |
2 |
| Condensing water heater versus standard tank-type
water heater |
240 therms |
28% |
(28.1%-
28.3%) |
$2400
(incremental) |
19.9 years (19.5-20.3) |
2 |
| Demand-based control of tank and recirculation
loop temperature versus constant aquastat control |
1,500therms |
16% |
(15.2%-
17.1%) |
$1400 |
1.9years
(1.6-2.2) |
3 |
| Time-based control of tank and recirculation
loop temperature versus constant aquastat control |
980 therms |
10% |
(8.1%-
12.9%) |
$940 |
2.2 years (1.3-3.0) |
3 |
| 1Savings are given as percentage
of whole-building gas use, except where noted. |
|
|
|
|
|
|
Acknowledgments
Most of the research reported in this article
was supported by Minnegasco, a Division of Arkla, Incorporated. The authors
gratefully acknowledge Minnegasco's long-term commitment to research. Tests
of domestic hot water measures were supported largely by the St. Paul Energy
and Environmental Resource Center, through a grant of oil overcharge funds
distributed through the Minnesota Department of Administration.
Further Reading
Biederman, N. and Katrakis, J. Space Heating
Improvements in Multi-Family Buildings, GRI-88/0111. Chicago: Gas Research
Institute, 1989.
Ewing, G., et al. "Effectiveness of Boiler
Control Retrofits on Small Multifamily Buildings in Wisconsin," Proceedings
of the American Council for an Energy Efficient Economy 1988 Summer Study
on Energy Efficiency in Buildings, V2, p. 2.51-2.56. ACEEE, 2140 Shattuck
Ave., Suite 202, Berkeley, CA 94704.
Goldman, C., Greely, K., Harris, J. Retrofit
Experience in Multifamily Buildings: Energy Savings, Costs and Economics,
LBL-25248. Berkeley, CA: Lawrence Berkeley Laboratory, 1988.
Hewett, M., Emslander, H., Koehler, M. "Heating
Cost Allocation in Multi-family Buildings: Energy Savings and Implementation
Standards." ASHRAE Transactions 95, pt. 1 (1989): 789-797.
Landry, R., et al. "Field Validation of
Diagnostic Techniques for Estimating Boiler Part-load Efficiency."
ASHRAE Transactions, 100, pt. 1 (1994): 859-875.
Lobenstein, M. S., Dunsworth, T., Hewett, M.
"Energy Savings and Field Experience from Converting Steam-heated
Buildings to Hydronic Heat." ASHRAE Transactions 99, pt. 1
(1993): 1282-1290.
Lobenstein, M.S., et al. "Field Testing
of Various Energy-saving Measures for Domestic Hot Water Heating in Multifamily
Buildings." In Proceedings of the American Council for an Energy
Efficient Economy 1992 Summer Study on Energy Efficiency in Buildings,
2, 2.145-2.155. Berkeley, CA: ACEEE, 1992.
Mary Sue Lobenstein is an engineering analyst
and Martha Hewett is a senior research analyst at the Center for Energy
and Environment, a Minneapolis nonprofit organization focused on applied
research and on the design, implementation, and monitoring of innovative
energy efficiency programs.
|