|
| Back to Contents Page |
Home Energy Index |
About Home Energy |
| Home Energy Home Page | Back Issues of Home Energy |
Home Energy Magazine Online May/June 1995
Measuring the Performance of the
National Energy Audit
A field test conducted in North Carolina demonstrates
significant performance improvements that the National Energy Audit (NEAT)
offers compared with Project Retro-Tech, and helps show that state-of-the-art
weatherization methods have come a long way.
|
In 1978, the U.S.
Department of Energy (DOE) published Project Retro-Tech to provide all
states a manual technique for identifying low-income weatherization measures
that would produce the most energy savings per dollar spent. While Project
Retro-Tech was considered a significant advancement at the time, it
focused only on a small number of shell measures and relied upon broad
assumptions and limited analytical capabilities because of its manual calculations.
In addition, these manual calculation requirements were challenging and
time consuming for auditors.
During the 1980s, a few states began to incorporate
promising new technologies into their weatherization programs. Many of
these new additions offered dramatic performance improvements over Retro-Tech
alone. Simultaneously, two large demonstration tests in Wisconsin and New
York incorporating advanced measures, techniques, and evaluation methods
showed that weatherization performance could be doubled without significantly
increasing costs. Federal regulations are now encouraging states to use
more advanced weatherization technologies. An advanced measure-selection
method developed by Oak Ridge National Laboratory and currently being used
by many states, is the National Energy Audit--NEAT (see
"Computerized Energy Audits," HE May/June '94 p.27).
The transition from the preliminary to the current
version of NEAT required expansion to national application and many additions
to meet the needs of potential users, but there were few changes to its
design fundamentals. Between 1989 and 1991 we tested the preliminary version
of NEAT alongside North Carolina's Retro-Tech-based weatherization program.
The cooperative test involved DOE, the State of North Carolina, the Alliance
to Save Energy, and three local weatherization agencies.
Retro-Tech-Based Weatherizations
In 1989, North Carolina's Retro-Tech-based program
was limited to the following measures (sometimes called "the big six")
in order of their installation priority:
- Infiltration measures
- Attic insulation
- Water heater, pipe, and floor insulation
- Duct insulation
- Underpinning (enclose the crawl space)
- Storm windows and storm doors
Each measure was installed until the allotted
funds, up to $1,400 per house on average (including administration costs),
were expended or the next consecutive measure was deemed unaffordable.
Needed infiltration (air sealing) measures were identified by the auditor
and included caulking, adding or replacing weatherstripping, repairing
or replacing windows and doors, and other repairs. Attic insulation was
installed to a minimum of R-19 and a maximum of R-30. R-11 or R-19 floor
insulation was installed.
The Advanced Field Test Audit (FTA)
In contrast to Project Retro-Tech, NEAT is a
computer-based audit that addresses many shell and equipment measures aimed
at reducing both space heating and cooling energy. Instead of a set list
of priorities, NEAT evaluates the expected performance of each measure
according to the needs of the individual house. The program ranks measures
by their benefit-to-cost ratio (BCR), adjusts this ranking for interactions
between measures (very important where both mechanical and shell measures
are installed), and provides a final list of recommended measures with
a benefit-to-cost ratio greater than one. The program quantifies costs
and savings, and recommends measures within seconds.
NEAT considers local costs (labor, materials,
and fuel), measure savings (both heating and cooling), measure life, and
the current discount rate. Local costs, house descriptive details (size
and construction), equipment details, and results from diagnostic measurements
(air leakage and heating system efficiency)--if made--are provided as input
by the auditor. The preliminary version of NEAT, the advanced Field Test
Audit (FTA) used in the North Carolina study, contained all of these features.
Air sealing in FTA-treated houses was done independent
of the FTA using a blower-door-directed procedure and a cost-effectiveness
guideline ( see "Blower Door Guidelines for Cost-Effective
Air Sealing,"HE Mar/Apr '90 p.34). A cutoff of 75 CFM50 (cubic feet
per minute at 50 Pascals house depressurization) air leakage reduction
per person-hour of labor was used for cost effectiveness and a minimum
ventilation guideline of 1,500 CFM50 was used for sealing.
Auditors also made decisions about heating system
tune-ups outside of the FTA, based upon steady-state efficiencies determined
from actual flue gas measurements on each system. (These decisions can
now be done within NEAT.)
 |
| Figure 1. Installed measures with frequencies
greater than or equal to 10% in either group. |
Field Test Design
The test began with 120 houses at three weatherization
agencies (sites). Houses were heated by kerosene, fuel oil, natural gas,
or propane, and had one or two operating window air conditioners. Houses
were split into three groups of 40 representing FTA, Retro-Tech, and control
groups, with each of the three test sites represented approximately equally
(13 or 14 houses per site in each group). We monitored weekly space heating
and cooling energy use and hourly indoor and outdoor temperatures between
November 1989 and September 1990 (pre-period) and between December 1990
and August 1991 (post-period).
We created linear models of measured heating
and cooling energy consumption as a function of average indoor-outdoor
temperature difference and weather-normalized them to adjust for differences
in average seasonal temperatures between the two monitoring periods.
We determined energy savings from the differences between pre- and
post-weatherization normalized consumptions.
Installed Measures
Of the 24 measures considered in the two weatherization
procedures, Retro-Tech considered 10, while FTA weatherizations considered
21 (see Table 1). Of these 21, the FTA made the installation decision for
17. The FTA considered shell and mechanical equipment measures that the
Retro-Tech audit did not.
Attic, wall, and floor insulations dominated
the FTA-recommended measures and were installed in 40%-70% of all houses
in this group. Attic and floor insulations dominated Retro-Tech-recommended
measures in quantities similar to the FTA group (when both floor R-19 and
R-11 insulations are combined). The largest differences were for wall insulation
and storm windows. Retro-Tech did not install wall insulation (because
it was not an option), but the FTA recommended it nearly half of the time.
In addition, Retro-Tech weatherizations resulted in new storm windows on
more than 80% of all houses, while less than 5% received storm windows
in the FTA group (due to poor window condition--not FTA-recommended).
The FTA installed R-30 in all uninsulated attics
and either none, R-11, or R-30 in those with insulation (the FTA did not
consider R-19 at the time). The Retro-Tech procedure filled all attics
to an R-30 level, independent of the existing attic insulation level. Except
for infiltration reduction, attic, wall, and floor insulation, and storm
window measures, neither audit called for the installation of any other
measure in greater than 11% of their respective houses.
The FTA recommended very few heating system measures.
This was primarily due to the abundance of space heaters (used for primary
heating in nearly 70% of all houses), which were not considered compatible
with most heating system measures. A replacement air conditioner was recommended
for one house (3%), but this house dropped out of the test before it was
weatherized.
The percentages of FTA houses receiving some
measures were very high based on the number of houses that could actually
have the measures installed (only houses with central furnaces for "smart"
thermostats, with accessible wall cavities and floors for wall and floor
insulation, and so forth). Attic, wall, and floor insulations were recommended
for more than 80%, kneewall insulation was always recommended, and smart
thermostats were recommended for 57%.
Air Sealing Results
We estimated air leakage rates at 50 Pa depressurization
in all houses before and after weatherization. Estimates were determined
from multiple blower-door measurements and a regression-based estimation
procedure similar to that specified by ASTM Standard E779-81. The best
linear fit of air leakage rates measured at five different house depressurizations
between 20 and 60 Pa was used to estimate house air leakage rate at 50
Pa. For high-leakage houses, those that could not be depressurized to 50
Pa, air leakage rates at 50 Pa were extrapolated from regression models
based on five measurements made below 50 Pa.
The average pre-weatherization air leakage rate
for all groups was 4,300 CFM50. Individual group averages were within 5%
of this value. Post-weatherization measurements were not completed in the
control group at two sites. As a result, reported air leakage reductions
represent 12 houses in the control group, 36 in the FTA group, and 37 in
the Retro-Tech group. The average air leakage reduction was 89 CFM50 for
the control group (no treatment), 1,710 CFM50 for the FTA group, and 716
CFM50 for the Retro-Tech group. Adjusting for the control group, reductions
of 37% were achieved in the FTA group, compared to 16% in the Retro-Tech
group. The average leakage reduction of the control group was within the
expected error of blower door test measurement.
Space Heating
Sixteen of the original 120 houses were removed
from the heating energy savings analysis due to attrition and other data
problems. We chose 65 of the remaining houses for a heating analysis, after
using a statistical analysis to screen out those with unreliable data (see
"Now That I've Run PRISM, What Do I Do with the Results," HE Sept/Oct '90,
p. 27). Generally, unreliable models occurred where the consumption
data were highly scattered (nine or fewer data points available for either
period) or represented only a small range of expected seasonal temperatures.
Weather-normalized, pre-weatherization space-heating
energy consumption averaged 50 MBtu (around $350 at $7/MBtu) for all 65
houses, and the three group averages were within 3% of this value. Space-heating
energy savings occurred for 89% of the FTA group and 87% of the Retro-Tech
group.
Individual space-heating savings of the 65 houses
ranged from a low of -33 MBtu (an increase in energy use) to a high of
53 MBtu. Average savings for control houses was -2.7 MBtu (-5%). Average
energy savings for the two weatherized groups were much larger, 13.9 MBtu
(28%) for the FTA group and 8.9 MBtu (18%) for the Retro-Tech group (see
Table 2). Adjusted for the control group, FTA weatherizations saved 33%
and Retro-Tech weatherizations saved 23%. This represents a performance
improvement of 43% over Retro-Tech-based weatherizations.

Space Cooling
Twenty houses were removed from the air conditioning
sample due to attrition and as in the heating energy analysis, many cooling
energy models were found to be unreliable. Houses with unreliable models
were not removed from the cooling analysis, however, because the lower
reliabilities resulted from the minimal and random use of air conditioning
in North Carolina's low-income houses--not data problems.
Weather-normalized, pre-weatherization space-cooling
energy consumption ranged from 0-4,867 kWh. The average pre-weatherization
cooling energy use for the 100 houses was 781 kWh (around $66 at $0.085/kWh);
the three group averages were all within 13% of this value. Most houses
in the test were very low cooling energy users. Approximately one of every
two houses (47%) used less than 500 kWh ($43) before weatherization. Only
14% used more than 1,500 kWh ($128).
The average cooling energy savings was 8 kWh
(1%) for the control group, 30 kWh (4%) for the Retro-Tech group, and 165
kWh (19%) for the FTA group. When adjusted for the control group change,
the FTA group saved 18% (net savings), which is much higher than the 3%
net savings for the Retro-Tech group. However, wide variances for the cooling
energy savings of individual houses preclude saying there is a statistical
difference between savings of the control and Retro-Tech groups.
Weatherization Costs
Although average weatherization costs for each
group are almost identical ($1,056 versus $1,059) individual site averages
are very different (see Table 3). Average FTA weatherization
cost was 14% less at Site A, 7% less at Site B, and a dramatic 38% higher
at Site C. Retro-Tech weatherizations at Site C also cost much less than
Retro-Tech weatherizations at the other two sites (around 40% less). For
Retro-Tech weatherizations, attic and floor insulation measures were much
more common at Sites A and B than at Site C.
Individual house weatherization costs in the
FTA group were more widely distributed. Approximately 90% of the Retro-Tech-based
weatherizations cost between $500 and $1,500, while only about 70% of the
FTA weatherization costs were within this range. Also, no Retro-Tech-based
weatherization cost more than $2,000, while four houses (11%) exceeded
this expenditure in the FTA group. The percent of weatherization dollars
spent on labor costs (including labor for repairs and air sealing) was
about the same, as shown in Figure 2. Thus, total material expenditures
were similar, but the proportions spent on the different measures varied
dramatically. Insulating materials in FTA houses accounted for about 34%
of costs compared to only 18% in the Retro-Tech houses. Storm windows,
which accounted for approximately one-third of all material costs in the
Retro-Tech houses, were almost unrepresented in the FTA material costs
(less than 2%).
 |
| Figure 2. Comparison of costs for the two weatherization
approaches. (Note: costs other than the labor column are for materials
only.) |

In Table 4, we compared the performance of the
two weatherization approaches to statisticsfrom past evaluations of standard
weatherization programs and the three demonstration programs that represent
the progression of NEAT technology. The performance of both standard and
demonstration programs has been improving over time. The National Evaluation
for 1989 indicates that standard program performance improved about 80%
in eight years. In Wisconsin, however, weatherization performance had almost
doubled in a demonstration program as early as 1985. More recent demonstrations
in New York and North Carolina suggest that a standard program performance
of 10% could be doubled and perhaps tripled by application of newer technologies.
Also, while heating energy savings are increasing, average weatherization
costs are decreasing. The 33% heating energy savings in North Carolina
is particularly noteworthy because heating energy savings in warm climates
are traditionally lower than the national average.
NEAT in '95
Today, NEAT uses weather data from 215 weather
stations across the country to evaluate measures for 48 states (Alaska
and Hawaii to be added as needed). While the fundamentals of how NEAT evaluates
and prioritizes measures has seen only small change since the preliminary
version, NEAT has undergone dramatic change based on needs indicated by
current and potential users. Perhaps its most important area of change
is in ease of use. Elements include recall of past building descriptions
for editing or reuse; pop-up screens that ease data entry; duplicate, erase,
and move features that allow building components to be rapidly described
or changed; built-in capabilities to minimize user errors; defaults where
measured values or equipment nameplate specifications are unavailable;
and the ability for users to define their own measures.
Important equipment additions include the ability
to address steam and hot water boilers, heat pumps, evaporative coolers,
mandatory and optional heating system replacements, heating system tune-ups,
and sizing for new heating systems. Other important capabilities include
the ability to use billing data for comparison to or modification of NEAT
results; to incorporate repair, health and safety, and miscellaneous costs
into the weatherization package as appropriate; and to evaluate the energy
savings and cost-effectiveness of air-sealing work.
NEAT is now a refined measure selection tool
that can be easily tailored for local use. It addresses the wide range
of measures and incorporates sophisticated analytical capabilities that
are needed to advance weatherization performance nationwide. Hundreds of
improvements have resulted from the recommendations of North Carolina users
and others in states that have more recently evaluated NEAT for their programs.
The measure evaluation technology in NEAT pushes
the most cost-effective of a large number of both heating and cooling measures
to the highest installation priorities. As a result, it is adding new measures
and excluding some measures that are traditionally installed in many state
weatherization programs. In turn, changes in where dollars are spent and
how they are distributed across houses are occurring.
Like other audits, NEAT is dependent on the well-trained
auditor and does not solve all of the auditor's challenges. It is, however,
a very valuable tool that can be incorporated into a state program to achieve
substantial and perhaps dramatic improvements in weatherization performance.
And most importantly, this can be accomplished without increasing costs.
References
M. A. Brown et al. "National Impacts of the Weatherization
Assistance Program in Single-Family and Small Multi-Family Dwellings,"
ORNL/CON-326. Oak Ridge, TN: Oak Ridge National Laboratory, May 1993.
McCold, L. N. et al. "Field Test Evaluation of
Conservation Retrofits of Low-Income, Single-Family Buildings in Wisconsin:
Audit Field Test Implementation and Results," ORNL/CON-228/P2. Oak Ridge,
TN: Oak Ridge National Laboratory, June 1988.
Sharp, T. R. "The North Carolina Field Test:
Field Performance of the Preliminary Version of an Advanced Weatherization
Audit for the Department of Energy's Weatherization Assistance Program,"
ORNL/CON-362. Oak Ridge, TN: Oak Ridge National Laboratory, July 1993.
M. P. Ternes et al. "The National Fuel End-Use
Efficiency Field Test: Energy Savings and Performance of an Improved Energy
Conservation Measure Selection Technique," ORNL/ CON-303. Oak Ridge, TN:
Oak Ridge National Laboratory, January 1991.
| Terry Sharp is a building energy researcher
with Oak Ridge National Laboratory in Tennessee. |
| The publication of this article in Home
Energy was underwritten in part by the U.S. Department of Energy's
Office of Energy Efficiency and Renewable Energy. |
|