|
| Back to Contents Page
| Home Energy Index | About
Home Energy |
| Home Energy Home
Page | Back Issues of Home Energy
|
Home Energy Magazine Online May/June 1995
Bigger is Not Better:
A colleague of
ours (we will call him Bill) approached us at a conference seeking
advice on selecting an air conditioner for his renovated home.
Our recommendations included, "Be sure that the cooling load
is calculated and that the air conditioner is sized to that
load." When Bill attempted to follow these instructions, only
one of the four contractors would submit a sizing calculation
(two others just wanted to know how many square feet there were
in the house). Bill hired the contractor who did the calculation
and installed a high-efficiency four-ton unit. Is this a success
story? Not really.
The contractor calculated a total cooling
load of 37,580 Btus per hour at 105°F outside and 70°F
inside. While the cooling load he calculated could have been
met by a three-and-a-half ton air conditioner, the contractor
convinced Bill to buy a four-ton unit "because then you will
always have plenty of cooling."
Bill's air conditioner short-cycles
(cycles on and off more often and for shorter periods of time
than it should) even during the hottest weather and removes
very little moisture from the air. What went wrong? Four things:
- The design temperature for the area is 97°F. The contractor
increased the outside design temperature by 8°F.
- The recommended design indoor temperature is 75°F. The
indoor temperature was lowered by 5°F. The temperature
- "fudges" increased the inside to outside differential by
59%.
- The contractor increased the calculated load by 20% as a
safety factor.
- The equipment selected was a half-ton larger than the next
highest available size to meet the load he calculated.
A three-and-a-half ton air conditioner
would have been perfect for Bill's house. Instead he paid more
for an extra half-ton of cooling. In addition to costing more
to buy, Bill's air conditioner will use more energy than a properly
sized system, raising his utility bills. It won't dehumidify
the air as well as a smaller system would, and chances are that
Bill will be less comfortable. The utility, which gave Bill
a rebate for his purchase, will also lose, since the oversized
unit aggravates summer peak-load requirements.
Key
Cooling Terms
Sensible Cooling Load
- The heat gain of the home due to conduction, solar
radiation, infiltration, appliances, people, and pets.
Burning a light bulb, for example, adds only sensible
load to the house. This sensible load raises the dry-bulb
temperature.
Dry-bulb Temperature -
The temperature measured by a standard thermometer.
Latent Cooling Load -
The net amount of moisture added to the inside air by
plants, people, cooking, infiltration, and any other
moisture source. The amount of moisture in the air can
be calculated from a combination of dry-bulb and wet-bulb
temperature measurements.
Wet-bulb Temperature
- When a wet wick is placed over a standard thermometer
and air is blown across the surface, the water evaporates
and cools the thermometer below the dry-bulb temperature.
This cooler temperature (called the wet-bulb temperature)
depends on how much moisture is in the air.
Design Conditions - Cooling
loads vary with inside and outside conditions. A set
of conditions specific to the local climate are necessary
to calculate the expected cooling load for a home. Inside
conditions of 75°F and 50% relative humidity are
usually recommended as a guideline. Outside conditions
are selected for the 2.5% design point.
2.5% Design - Outside
summer temperatures and coincident air moisture content
that will be exceeded only 2.5% of the hours from June
to September. In other words, 2.5% design conditions
are outdoor temperatures historically exceeded 73 out
of the 2,928 hours in these summer months.
Capacity - The capacity
of an air conditioner is measured by the amount of cooling
it can do when running continuously. The total capacity
is the sum of the latent capacity (ability to remove
moisture from the air) and sensible capacity (ability
to reduce the dry-bulb temperature). Each of these capacities
is rated in Btus per hour (Btu/h). The capacity depends
on the outside and inside conditions. As it gets hotter
outside (or cooler inside) the capacity drops. The capacity
at a standard set of conditions is often referred to
as "tons of cooling."
Tons of Cooling - Air
conditioner capacity is rated at 95°F outside with
an inside temperature of 80°F and 50% relative humidity.
Each ton of air conditioning is nominally 12,000 Btu/h
(this comes from the fact that it takes 12,000 Btu to
melt a ton of ice). While an air conditioner may be
called a three ton unit, it may not produce 36,000 Btu/h
in cooling. There is a wide variety of actual capacities
that are called "three tons."
EER - The Energy Efficiency
Ratio is the efficiency of the air conditioner. It is
capacity in Btu per hour divided by the electrical input
in watts. EER changes with the inside and outside conditions,
falling as the temperature difference between inside
and outside gets larger. EER should not be confused
with SEER.
SEER - The Seasonal Energy
Efficiency Ratio is a standard method of rating air
conditioners based on three tests. All three tests are
run at 80°F inside and 82°F outside. The first
test is run with humid indoor conditions, the second
with dry indoor conditions, and the third with dry conditions
cycling the air conditioner on for 6 minutes and off
for 24 minutes. The published SEER may not represent
the actual seasonal energy efficiency of an air conditioner
in your climate.
Manual J - Manual J is
a widely accepted method of calculating the sensible
and latent cooling (and heating) loads under design
conditions. It was jointly developed by the Air Conditioning
Contractors of America (ACCA) and the Air-Conditioning
and Refrigeration Institute (ARI).
Manual S - Manual S is
the ACCA method of selecting air conditioning equipment
to meet the design loads. It ensures that both the sensible
capacity and the latent capacity of the selected equipment
will be adequate to meet the cooling load.
Manual D - Manual D is
the ACCA method for designing duct systems. Contractors
often find it a laborious process and most duct systems
are just installed, not designed. The amount of time
necessary to design a duct system is certainly warranted
in tract construction where the design is used repeatedly
and for custom homes where the total cost of the home
warrants a proper design. In short, designing a duct
system is essential for proper equipment performance
and customer comfort. |
Selecting the Right Air
Conditioner for the Job
Before one can design an efficient and
effective air conditioning system, the load must first be calculated
using established techniques. The Air Conditioning Contractors
of America (ACCA) conducted an industry study of residential
cooling load calculations and developed Manual J to estimate
these loads (see "Calculating
Loads with Manual J," p.22). Manual J was adopted by ACCA
and the Air-Conditioning and Refrigeration Institute (ARI),
and is the standard method of sizing loads for residences.
ACCA has also produced Manual S for
selecting equipment and Manual D for duct design (revised in
January 1995). Manual S provides a method to select air conditioners
based on the estimated sensible and latent load calculated for
the particular house in the local climate.
If mistakes are made in the load calculations
or the sizing method is flawed or incorrect inputs are used,
the equipment will be incorrectly sized and will not perform
as it should. Field studies have shown that most equipment is
substantially oversized compared to Manual J specifications.
In the Model Energy Communities Project, Pacific Gas and Electric
Company (PG&E) found that 53% of the air conditioners checked
were a ton (12,000 Btu/h) or more oversized and a study by Pacific
Northwest Laboratories found a third of the air conditioners
to be a ton or more oversized.
Because of the efficiency penalty of
oversized air conditioners and because oversized air conditioners
contribute substantially to utility demand peaks, in 1994, PG&E
commissioned a study by Proctor Engineering Group to compare
common load calculations and sizing methodologies to Manual
J calculated values.
What is "Proper" AC Sizing?
Since optimum efficiency is achieved
at continuous running, it is important that the air conditioner
be sized to achieve the longest run times possible. Manual J
specifies use of the 2.5% design temperature as developed by
the American Society of Heating, Refrigeration, and Air-Conditioning
Engineers (ASHRAE). A theoretical perfectly-sized air conditioner
will run continuously for the 73 hours during the year when
the outdoor temperature is greater than the 2.5% design point.
For instance, a 2.5% summer design temperature of 100°F
for Fresno, California, means that the temperature generally
only exceeds 100°F for 73 hours in the season (0.025 x 2,928
hours in the months of June through September). During the rest
of the time the air conditioner will cycle and operate at less
than its potential efficiency.
A properly sized air conditioner should
provide maximum value to the customer as well as a reasonable
profit and further customer referrals for the contractor. If
your air conditioner is cycling even at four in the afternoon
on the hottest days, it is a sure sign it is oversized. Incidentally,
if the AC is running continuously on hot days, it doesn't necessarily
mean that it is undersized. It is possible that the duct system
is leaky, the air conditioner is improperly charged, or the
air flow across the inside coil is too low (see
"An Ounce of Prevention; Residential Cooling Repairs," HE May/June
'91 p. 23).
Why Are Air Conditioners
Oversized?
Customers depend on the expertise of
contractors in selecting an air conditioner. Yet contractors
generally size air conditioners at least a half-ton larger than
necessary and often oversize by a ton or more. Even the most
conscientious contractor is driven to avoid call-backs (or even
lawsuits). If the air conditioning system isn't working properly
(duct leaks, improper flow across the coils, improper charge)
then the oversized air conditioner can mask the problem. Unfortunately,
many customers think that "bigger is better," so in a competitive
situation, the contractor proposing the proper size unit may
lose the bid. Contractors are hesitant to adopt an unfamiliar
method of sizing when the methods they have developed over the
years have served them well: "I've done it this way for 30 years
and I've never had a complaint." It is no surprise then that
air conditioners are oversized; however, the advantages of a
properly sized air conditioner are so large that these barriers
need to be overcome. Customers pay a price for oversized air
conditioners, and in many climates, lose comfort as well.
A properly sized air conditioner costs
the customer less (see Figure 1). Bill's
air conditioner cost him more money because it was too big.
The contractor had the opportunity to discuss the value of the
air conditioner based on the delivered efficiency and offer
Bill equipment at a lower cost. He missed the opportunity.
 |
 |
| Figure 1. Initial
air conditioner cost (quoted wholesale). |
Figure 2. Air
conditioner efficiency versus run time. |
Air conditioners are very inefficient
when they first start operation. It is far better for the air
conditioner to run longer cycles than shorter ones. The efficiency
of the typical air conditioner increases the longer it runs
(see Figure 2). If the on-time of the
air conditioner is only 5 minutes (a fairly typical run time)
the efficiency (EER) is 6.2. If, on the other hand, a properly
sized air conditioner were used (one 50% smaller), the same
amount of cooling would take place in less than 10 minutes,
and the efficiency would rise to 6.9. This represents a savings
of 10% for the customer. Most of the cooling season the cooling
loads are well below the capacity of properly sized air conditioners,
and for oversized units the short cycling is a substantial problem.
Because of the short cycles, Bill's high-efficiency air conditioner
is less efficient.
The ability of the air conditioner to
remove moisture (latent capacity) is lowest at the beginning
of the air conditioner cycle. The moisture removed from the
indoor air is dependent upon the indoor coil temperature being
below the dew-point temperature of the air. The moisture then
wets the indoor coil and, should the unit run long enough, will
begin to flow off the coil and be removed out of the condensate
drain. For short cycles, the coil does not have time to operate
at the low temperature and when the unit stops, the moisture
on the coil evaporates back into the indoor air. Thus, in humid
climates, a properly sized air conditioner will do a far better
job of removing moisture from the air than oversized units.
Bill's oversized air conditioner could not remove enough moisture
from the air, so his house was cold and clammy.
In addition, the speed of the air blowing
through the supply registers and the air being drawn into the
return grille affects an air conditioner's performance. If the
air speed is too high, it will be noisy and uncomfortable, and
the return grille filter effectiveness will be reduced. The
speed through the grilles depends on the size of the air conditioner
(a larger unit has more air flow and higher air speed) and the
area of the grille (a smaller grille causes higher air speed).
With a properly sized air conditioner, it is easier to have
sufficient supply and return grille area to keep the air speed
low and the noise at a minimum. Common complaints about oversized
air conditioners are that they blast frigid air and that they
are noisy. A properly sized air conditioner, with proper ductwork
and grilles, will provide longer cycles, more consistent temperatures,
and better mixing of the house air.
ACCA Manual D specifies a maximum return
grille velocity of less than 500 ft per minute and a maximum
supply outlet of less than 700 ft per minute. Figure 3 shows
that for a standard 2' x 2' return grille, the 500 ft per minute
requirement is exceeded with all units over 21/2 tons, with
the resulting increase in noise.
|

|
| Figure 3. Air speed for a standard
2 ft x 2 ft return grille. |
Calculating
Cooling Loads with Manual J
Manual J is a method of calculating
the cooling and heating loads for a single family residence.
It calculates room by room loads for duct design purposes,
and whole house loads for equipment selection purposes.
It was jointly developed by the Air-Conditioning Contractors
of America (ACCA) and the Air-Conditioning and Refrigeration
Institute (ARI) after ACCA conducted an industry study
of residential load calculations. Manual J procedures
are based on a number of sources including the ASHRAE
Handbook of Fundamentals. The basic structure of Manual
J is:
Heat Gain (Btu/h) = HTM x Area
where HTM is a Heat Transfer Multiplier (in Btu/h/ft2).
Area is the area of the building component (such as
a wall).
The HTMs take into account orientation,
shading, temperature difference, solar gain, thermal
storage, diurnal temperature swing, construction, R-Values,
and roof color.
Manual J is a simplified adaptation
of more complex modeling, yet it does not make many
of the gross assumptions that some other load calculation
methods use. It estimates both the latent and sensible
cooling loads (both are necessary to properly size a
system).
It is the result of a process
that involved a large part of the HVAC industry and
is widely accepted. It is in fact the basis for many
of the other methods that are used, including many of
the computer programs. For the contractor it is "safe."
Because contractors helped develop it, any compromises
that were made were not in the direction of undersizing
units.
Manual J bases the infiltration
rate on floor area and Best, Average, or Poor construction,
but far better models of infiltration exist based on
blower door testing. Manual J also does not have a method
of considering duct leakage (although the new Manual
D discusses duct leakage at some length and recommends
that duct leakage be eliminated, not calculated). The
existing duct leakage in homes consumes some (but usually
not all) of the safety margin built into Manual J. If
duct leakage were brought under control, units could
be sized smaller than Manual J.
While Manual J is simplified,
it is still not simple. Because of the many values and
tables, it is easy to make an error when using it. In
most cases, either a set of tables specific to the contractor's
service area, or a computer program should be used to
reduce the likelihood of errors. The Florida Solar Energy
Center is developing a more simplified sizing methodology
for Florida that compares favorably with Manual J results.
While individuals who have used Manual J extensively
are convinced that it has a substantial oversizing margin,
there are no field studies that have determined the
size of that margin. |
Sizing Up the Sizing Calculations
To qualify for PG&E's air conditioner
rebates in 1994, contractors were required to submit their load
calculation methods, and they had to submit the actual calcuations,
for approval for each job. We compared over 40 different load
calculation methods submitted by manufacturers, distributors,
and contractors to Manual J. Manual J was used as a baseline
because it is the most widely accepted load calculation methodology
and is generally recognized as providing a safe estimate of
cooling load. (Some experts believe Manual J consistently overestimates
the load by about 20%, as a built-in "safety" factor.)
In the second part of the study, Proctor
Engineering Group compared four different equipment selection
methods to determine how close the selected equipment capacity
came to the calculated load. The capacity of an air conditioner
is dependent not only on the outdoor conditions, but also on
the actual indoor conditions (temperature and humidity). Proctor
Engineering Group developed a procedure for estimating the expected
indoor humidity at design conditions. By knowing both indoor
and outdoor conditions, the capacity of the selected air conditioner
was determined.
For both parts of the study, loads were
calculated for buildings of different age and construction in
two different climate zones.
Most Contractors Oversize
The submitted calculations were all
over the place (see Figure 4). In the
extreme, the calculated load was three times the Manual J calculated
load.
 |
|
Figure 4. Examples of submitted
load calculation results.
|
Of the 40 load calculations that were
submitted, we approved those that yielded building loads within
20% of Manual J as received. This group included four worksheets,
one calculator method, and five computer programs. The approval
process was interactive and led to many stimulating conversations.
David, a contractor for over 20 years, shared some of the "seat
of the pants" methods he had observed through the years. One
method was to "buy the distributor's overstock," another was
to "install the rejected unit from a previous job," and still
another was to "install the unit sitting in the truck or at
the shop." David referred to these methods as "sizing by cost."
Contractors submitted methods that they
sincerely believed would properly size air conditioners. Some
of the methods, however, were based on information from as long
ago as 40 years. These methods did not take into account the
latest efficiency developments in building insulation, windows,
and air tightness. The methods were often handed down from the
person who taught them the business. "I learned this from my
father and it has always worked." Since the contractors had
received few or no complaints of inadequate cooling, they considered
their methods sufficient. Unfortunately, they were significantly
oversizing units--particularly on newer more energy-efficient
homes.
In an effort to properly determine cooling
load, some contractors had spent good money on computer programs,
had developed their own methods from books in the library, or
borrowed from other contractors in the area. Proctor Engineering
and PG&E worked with these contractors to find ways to bring
their methods within 20% of Manual J. With changes, an additional
ten methods were approved. This second group included seven
worksheets, one calculator method, and two computer programs.
Altogether, 50% of the submitted methods were approved for use
in PG&E's service territory. Methods that will calculate
loads within 20% of Manual J will vary with the climate because
of the way latent loads are treated. Of the approved computer
methods, RHVAC from Elite Software was the most user friendly.
Right-J from Wright Associates faithfully followed ACCA Manual
J.
A number of the methods did not calculate
the latent load of the home. Many assumed that the latent load
was 30% of the sensible load. The actual latent load is highly
dependent on the air tightness of the home, the local climate,
and the interior moisture sources (such as people). For hot,
dry climates, the latent load will be far less than 30%, particularly
if the house has a large amount of air leakage from the attic.
For humid climates, the latent load can be higher than 30% of
the sensible load if the house has a significant amount of air
leakage.
In all cases, infiltration loads (air
leakage) were not specifically addressed or were calculated
by an oversimplified procedure. Contractors often assumed that
infiltration rates were the same in all buildings or only depended
on floor area. With the widespread use of blower door testing,
we now know that homes vary significantly in their leakage rate.
With the amount of data required to
do an accurate load calculation, the possibility of errors is
increased. Even the computerized methods of load calculation
were seriously lacking in error checking procedures that could
catch operator errors. For example, window areas can exceed
wall areas, or wall areas facing north can be one square foot
with a south wall of 300 ft2 and east and west walls of 200
ft2. Many of the methods also oversimplified the process and
gave insufficient options for climate, building assemblies (windows,
doors, walls, etc.), and shading.
The effect of duct leakage has only
recently been investigated to any significant extent. As a result,
cooling loads due to duct leakage are not included in any of
the methods. Duct leakage has three effects on design cooling
load. First, a supply leak is a direct loss in capacity. Second,
a return leak will often bring in superheated attic air. Third,
the difference between supply leakage and return leakage will
cause increased infiltration. While it is tempting to treat
duct leakage as additional infiltration, the effect is actually
more complex.
How should the loss due to duct leakage
be taken into consideration when an air conditioner is sized?
The answer of course is simple. Don't take duct leakage into
account--fix the leaks!
Sizing by the Square Foot
The "square-foot-per-ton" sizing method
avoids calculating the cooling load of the building and proceeds
directly from the square footage of the building to the size
of the air conditioner. No contractor submitted such a method
for approval but a number of contractors reported that they
often used this method, or knew others who did. In a study by
the Florida Solar Energy Center 25% of the contractors reported
that they size by floor area (see
"How They Size Air Conditioning Systems in Florida," ).
While this approach is rapid and simple, it does not account
for orientation of the walls and windows, the difference in
surface area between a one-story and a two-story home of the
same floor area, the differences in insulation and air leakage
between different buildings, the number of occupants, and many
other factors. In some cases contractors attempt to cover these
variables by categorizing the home as low (a new home in a moderate
climate), average, or high (an old home in a hot climate) but
this method also falls short of properly sizing air conditioners.
Figure 5 was produced with those types of categorizations.
 |
 |
|
Figure 5. Sizing by house floor
area.
|
Figure 6. Manual S selection from
Manual J loads.
|
Selecting Equipment with
Manual S
Manual J (or other methods) gives a
contractor both the sensible and latent design loads for the
house. A common, but wrong, practice is to then divide the total
cooling load by 12,000 Btu/h per ton and choose an air conditioner
with that nominal tonnage. Nominal tonnage, however, does not
indicate capacity under differing design conditions. Manual
S provides a process for selecting equipment that will meet
the sensible and latent load at Manual J design conditions.
It guides the user to select an air conditioner that has a sensible
capacity between 100% and 115% of the calculated sensible load.
It further specifies that the latent capacity must exceed the
calculated latent load. For example if the calculated design
load was 20,530 Btu/h sensible and 1,380 Btu/h latent, an air
conditioner with capacities of 22,100 Btu/h sensible and 9,300
Btu/h latent might be chosen (108% of sensible load and 674%
of latent load).
The result of this method will be an
oversized air conditioner. Design indoor conditions for Manual
S are 75°F and 50% relative humidity. The actual indoor
relative humidity at design in much of the western United States
(including California, Nevada, Arizona, New Mexico, and parts
of Texas) is closer to 35%.
Air conditioner sensible capacity increases
with drier indoor air. Under design outdoor conditions in Las
Vegas, the actual capacity of our example air conditioner is
26,860 Btu/h sensible and 1,805 Btu/h latent (131% of load).
In this example, Manual S results in an air conditioner that
is 31% oversized. Both Manual J and Manual S are safe methods.
If these two methods are applied there is no reason to add additional
"safety factors" when selecting air conditioning equipment.
Problems with Manufacturer's
Data
Air conditioners selected based on standard
indoor conditions of 80°F with 50% relative humidity (which
is the standard ARI capacity rating condition) will be incorrectly
sized for 75°F. Unfortunately, many of the major manufacturers
provide information only at 80°F. It would be a great improvement
if the manufacturers provided tables that presented the sensible
and latent capacities at 75°F for a variety of indoor humidities.
How They Size
Air Conditioning Systems In Florida
To determine actual practices used by contractors to
size air conditioners, researchers with the Florida
Solar Energy Center recently surveyed the 450 members
of the Florida Air Conditioning Contractors Association
and sent surveys to a general list of 5,559 HVAC contractors.*
The overall response rate was a respectable 9%. An analysis
of the survey results found that the following typifies
residential sizing practices in that state.
- Sizing is accomplished using Manual J by 33% of
the respondents, software is used by 34% of the respondents,
square footage is used by 24%, and "other" procedures
are used by 8%. Generally, respondents who are not
members of ACCA were much more likely to use square
footage or "other" procedures.
- Of the respondents reporting "other" methods, 29%
use a utility's short form, 26% use their own calculations,
19% use load sheets or manuals, 11% hire others, and
14% use personal experience or other methods.
- Of 127 contractors indicating the square feet they
estimate per ton for AC sizing, the most common response
(36.2%) was 500 ft2. The range was from 350 to 700
ft2 per ton and the average was 502 ft2 per ton.
- Fifty-two percent of respondents use a room-by-room
method of sizing, 41% use whole house, and 6% use
other methods.
- Air-flow calculations for each room are done with
square footage estimation by 30%, with software by
22%, with Manual D by 20%, with CFM-per-ton by 18%,
and with other methods by 10%.
- Of the 79 contractors providing a CFM per ft2 estimate,
42 of them (53%) use 1.0 CFM per ft2--but with a great
deal of variability. A value of .8 CFM per ft2 was
the second most common response (10%) and a value
of 1.5 CFM per ft2 was the next most popular response.
- Construction drawings are used for obtaining take-off
measurements by 62% of the respondents with 23% making
their own measurements at the site, and 10% not using
take-offs.
Inaccurate Sizing Methods?
When asked about contractor experiences with inaccurate
sizing methods, some responses were humorous. One contractor
said "listening to the builder" was the most unreliable
method, while another indicated that "listening to the
homeowner" was equally problematic.
The survey indicated that sizing is fairly evenly split
between Manual J calculations, computer software, and
estimation by floor area. Not surprisingly, each camp
had strong opinions of the other methods. Many using
Manual J or computerized methods regarded square footage
as an inaccurate means of sizing.
Some of those using square footage mentioned that not
accounting for vaulted ceilings or large expanses of
glass could lead to low estimates. However, the square
footage camp strongly derided Manual J and computerized
methods for undersizing units. The most common reported
reason for the perceived failure of Manual J or computerized
methods was that customers desire lower temperatures
than Manual J assumes.
Nearly 40% of the respondents indicated that they have
at times purposely oversized units. Almost none purposefully
undersized units. Many indicated that they round up
predicted sizing by half a ton to allow for future expansion
or to "reduce callbacks." Of those who explained why
they oversize, over 30% indicated a customer request--often
a demand--for low temperatures. By far the most commonly
expressed reasons for oversizing were either to "provide
more cooling" or to lower temperatures. "I oversize
by 50%," indicated one contractor, "so customers will
not complain."
The survey also shows that some contractors use sizing
estimation values half again larger than others for
sizing units, and twice as large for determining room
air flow. The few respondents who did emphasize the
need to size units small, were completely outnumbered
by the "bigger-is-better" school.
* See "How Contractors Really Size Air Conditioning
Systems," by Robin K. Vieira, Danny S. Parker, Jon F.
Klongerbo, Jeffrey K. Sonne, and Jo Ellen Cummings,
Florida Solar Energy Center, 300 State Road 401, Cape
Canaveral, FL 32920. Tel:(407)783-0300. |
Recommendations for Consumers
There are contractors out there who
would like to do the job right. "I love to do houses but only
if we can do them properly. I try to work inexpensively, but
not cheaply.... No flex or triangles, thank you." (One contractor's
response in the FSEC Survey.) Consumers purchasing air conditioning
equipment should:
- Give the contractor the "Recommendations
for Contractors" that follows and insist that the list be
observed.
- If the contractor wants to size by
square footage, find another one. (There are no certification
organizations that meet our criteria, however the Florida
Solar Energy Center found that members of ACCA were half as
likely to use floor area to size an air conditioner as other
respondents.)
- Insist on a copy of the calculations
(or computer inputs and outputs)--even if you don't understand
them.
- Be willing to pay for the time the
contractor must spend to do the job right. Don't take the
lowest bid.
Recommendations for Contractors
- Check all numbers for consistency.
For example, in typical construction, total area of exterior
walls facing north or east (including a wall to garage) is
usually equal to the total area of the opposite south or west
walls; ceiling area is usually equal to the building footprint
area; window area is usually from 10% to 25% of the floor
area; gross wall area is bigger than the window area.
- Use design outdoor conditions and
daily temperature range exactly for your location per Manual
J or ASHRAE Handbook of Fundamentals. Otherwise, use the data
for the closest location with a similar climate.
- Use standard 75°F design indoor
temperature.
- Consider both location and level
of insulation of ducts.
- When selecting cooling factors for
roofs, floors, and walls consider their R-value and type;
for example, frame wall or masonry wall. Partitions and knee
walls that separate a conditioned space from an unconditioned
space like an attic or garage should be treated separately
from the exterior sunlit surfaces.
- Pay great attention to window type,
material, and interior shading. An error in this area can
throw off the window heat gain by as much as 100%.
- Always account for the effect of
the overhang shading. This is one of the most efficient load
reduction measures. When calculating this effect, consider
window height, overhang length and distance to the top of
the window as shown on page 30 of Manual J.
- Calculate infiltration rate depending
on air tightness of the building based on blower door measurements.
While you are at it, measure the duct leakage and suggest
that it be fixed before the air conditioner is installed.
- Calculate the latent load based on
the number of people and the outdoor air humidity ratio. Do
not use a "typical" multiplier of 1.3 or any other to calculate
the total load from the sensible load. This implies that every
building has a latent load that is exactly equal to 30% of
its sensible load and that the quality of construction and
location are not important. It also means that if a new source
of the cooling load is added, for example another window,
the moisture gains will also increase. This simply is not
accurate.
- Consider ventilation load if appropriate.
- Select equipment based on the detailed
manufacturer's performance data. Do not rely on the nominal
tonnage since different units may have more than 10% capacity
difference.
- Choose equipment based on the ACCA
Manual S without using any safety factors. This method selects
the unit that has the sensible capacity at least equal to
but no more than 15% greater than the building sensible load,
and the latent capacity equal to or greater than the latent
load at standard indoor conditions of 75°F dry bulb and
50% relative humidity. For dry climates, Manual S alone, oversizes
by approximately 20% compared to Manual J load.
- Properly evacuate the coil and refrigerant
lines before releasing the refrigerant charge from the outside
unit into the system (use a micron gauge).
- After installation, check the air
flow across the coil and the refrigerant charge using the
manufacturer's suggested methods. Correct any deficiencies.
| John Proctor is president
of Proctor Engineering Group in San Rafael, California.
Zinoviy Katsnelson is a senior research engineer with
Proctor Engineering Group. Brad Wilson is a senior program
development manager at Pacific Gas and Electric Company
in San Francisco, California. |
| This article is apart of a
series of energy-efficient remodeling, which is being
funded by the Environmental Protection Agency and the
Department of Energy. |
|