|
| Back to Contents Page |
Home Energy Index |
About Home Energy |
| Home Energy Home Page | Back Issues of Home Energy |
Home Energy Magazine Online March/April 1995
|
Ventilating Attics to
Minimize Icings at Eaves
Using outdoor air to ventilate
the space below a snow-covered steep roof is an effective way to avoid
icicles and ice dams.
|
|
|
 |
by
Wayne Tobiasson,
James Buska, and
Alan Greatorex
|
 |
| Two identically constructed roofs photographed at the
same time. The building with no icings was unheated. |
|
|
Icicles and ice dams form at the eaves of some
roofs in cold regions. Water that ponds behind ice dams may leak into the
building since most steep roofs are configured to shed water, not hold
back standing water.
The photographs above show two roofs of identically
constructed buildings located near Watertown, New York. They were taken
within minutes of each other. One roof contains large ice dams and icicles,
but the other is ice free. Why? The snow on top of the chimney of one roof
is the clue to the difference in behavior. That building was not being
heated while the other building was.
This example demonstrates that building heat,
not the sun, is the primary cause of ice dams and icicles on roofs. When
the sun melts snow on roofs it also warms the eaves, and this tends to
minimize the growth of icicles. Certainly some icicles can form on unheated
buildings and from solar heating, but they are usually small, infrequent,
and do not cause chronic problems.
Research conducted in 1976 at the University
of Minnesota concluded that a combination of insulation, ventilation, and
"correct house design" is needed to reduce ice dam formation.
Recent studies also promote use of "cold" ventilated roofing
systems to reduce icings at eaves. These studies also indicate that icings
can be reduced by increasing the slope of the roof, by making the surface
slippery so that snow slides off, by not installing gutters and by reducing
the overhang at the eaves. However, on roofs without gutters, too small
an overhang can cause wetting of the walls below or formation of icings
on them. A 12-inch overhang is often a good compromise in cold regions.
Also, allowing snow to slide off roofs can create hazards. Snow guards
may be needed to hold snow on slippery roofs.
Icicles Form in Upstate New York
A few years ago many office buildings, barracks,
and dining facilities were built at Fort Drum near Watertown, New York.
All of these buildings have standing seam metal roofing systems above ventilated
attics. Some of the roofs remain clear of icicles and ice dams, several
experience some problematic icicles and ice dams, and a few experience
severe icicles and ice damming. This range in performance is related to
the ability of each building's attic ventilation system to remove heat
that enters the attic from the warm building below and heat produced by
HVAC equipment located in the attic.
We are developing recommendations for solving
these specific problems and are attempting to better understand how and
when icicles and ice dams form. During our first winter of study (1990-91)
we monitored four buildings to determine their current performance before
modifications were made to improve the ventilation of their attics. We
selected the four buildings to study a range of icing problems from some
to severe. By "some" we mean minor icings had occurred along
the eaves and large problematic icings had developed at some locations
such as the base of valleys. A building with severe icings is shown below.
We also monitored a nearby building not experiencing icing problems as
a control.
The Measurements
We monitored the outside air temperature in a
small weather shelter in the vicinity of these buildings. Attic air temperature
was monitored near the middle of each attic. We took temperature measurements
once an hour from November into April. Battery-operated data collection
systems stored the data between our periodic visits.
Findings
Observations by ourselves and others indicate
that icings seldom grow when the outside temperature is above 22°F.
Plots of attic air temperature vs. outside air
temperature are presented in Figures 1 and 2 for buildings experiencing
no icing problems, and "severe" icing problems. Horizontal and
vertical lines representing, respectively, an attic air temperature of
30°F and an outside air temperature of 22°F are also presented on
each figure. The portion of each graph to the right of the vertical 22°F
line is warmer than conditions observed to create icings. The portion of
each graph below the 30°F horizontal line is also not within the "icing
envelope" because the attic is then so cold that snow on the roof
is not melted by building heat.
We chose 30°F for the horizontal line instead
of 32°F since we expect that there were places in the attics that were
somewhat warmer than the places where our temperature sensors were located.
Of the four quadrants created in Figures 1 and
2 by the 22°F vertical line and the 30°F horizontal line, the upper
left quadrant defines the problem area (the "icing envelope").
As we expected, for the roof with no icing problems
(Figure 1) very few data points fall within the icing envelope. For the
roof with "severe" icing problems (Figure 2
), 23% of the data
(23% of the time during the winter) falls within the "icing envelope."
The separate line of points in Figure 2 that
runs down toward the lower left corner of the graph represents a five-day
period when the heating system of that building was off due to mechanical
problems. Those points provide further evidence that building heat is the
primary source of icing problems since, once cool, that building performed
out of the "icing envelope."
The curves of best fit for these two roofs are
the upper and lower solid lines on Figure 3. The three lines between them
are for other buildings we monitored that also had "some" icing
problems. All this information suggests that icings can be avoided by sizing
attic ventilation systems to maintain an attic temperature of 30°F when
the outside temperature is 22°F.
 |
| Figure 1. Attic temperature versus outside air temperature for
a roof experiencing no icing problems. |
 |
| Figure 2. Attic temperature versus outside air temperature for
a roof experiencing severe icing problems. |
 |
| Figure 3. Lines of best fit for the roofs shown in Figures 1
(bottom line) and 2 (top line). The three circled lines are for other roofs
with "some" icing problems. |
Applications
The attic described by Figure 2 experienced severe
icing problems. However, it only needed help in the form of improved natural
ventilation or mechanical ventilation for less than 23% of the winter.
We were not able to provide enough inlet area to completely solve this
attic's icing problems using only natural ventilation. Thus several large
fans were installed near the ridge. The fans are not dampered. This allows
the fan openings to serve as outlets for natural ventilation, thereby reducing
the amount of time that mechanical ventilation is needed.
We installed instrumentation to monitor when
the fans are needed. The fans are thermostatically controlled, since they
are needed infrequently. They operate only when the attic temperature is
above 30°F and the outside temperature is below 22°F.
We monitored the modified building and a similar
unmodified building from November 1993 into February 1994 (see Figure
4). Both buildings were having similar severe icing problems before
one was modified. The portion of each data set to the right of the 22°F
outside air temperature line in Figure 4 relates to natural ventilation
since the fans cannot operate when it is warmer than 22°F outside. The
dramatic difference in that portion of the two data sets indicates that
natural ventilation has been improved significantly. We expect that much
of this improvement would not have been achieved if the fans contained
louvers that were opened only when the fans were on.
The "hunk" taken out of the data set
for the building with improved attic ventilation reflects the contribution
of the mechanical ventilation system. The mechanical system had been able
to keep that attic out of the "icing envelope" most of the time.
Without mechanical ventilation it appears that the attic would have operated
within the icing envelope for a significant amount of time with problematic
icings expected. This verified our feeling that natural ventilation alone
would not solve the icing problems being experienced by these buildings.
The pictures, below, show the two buildings on
the same date (January 12, 1994). The unmodified building is subjected
to severe icings all along its eaves. There are only a few small icicles
at the base of the valleys of the building with improved attic ventilation.
All other irregularities along the eaves of that roof are snow cornices,
not icicles.
Seven large fans were installed to mechanically
ventilate the modified attic. Each one consumes about one kilowatt of power.
Using the methodology we've described in "Design
Approach" (below), four of these fans would be enough to do the
job. So, in February we had three of the fans turned off and blocked with
sheet metal to preclude both mechanical and natural ventilation through
them.
The natural ventilation portion of the data for
openings provided by four fans did not change noticeably from that when
openings were provided by seven fans. The mechanical ventilation data indicates
that the four fans kept the attic out of the "icing envelope"
almost as well as the seven fans did. No large icings formed on the modified
building with only four of the seven fans working. These findings convince
us that the design approach presented in this article can be used to size
natural ventilation systems and, quite likely, also mechanical ventilation
systems for solving icing problems.
 |
| Figure 4. Attic temperature versus outside air temperature for
a building with severe icing problems and a similar building with improved
attic ventilation experiencing no icing problems. |
|
Design Approach
With knowledge of the thermal resistance of the
ceiling and the indoor and attic temperatures, the conductive heat losses
from a heated building into its attic can be determined. To this can be
added any heat introduced to the attic by HVAC equipment and any ducting
located there. If the assumption is made that during the design
condition, the roof is covered with an insulating blanket of snow that
reduces conductive heat losses from the attic to near zero, then all the
heat in the attic must be removed by ventilating air.
The following equation applies when the attic
air is 30°F and outside air is 22°F:
Q = 6.94 H(1)
where Q = airflow rate required to remove heat (cfm) and H
= heat to be removed (Btu/min).
If this airflow is to be provided by natural
stack effect with 22°F air entering the 30°F attic all along its
eaves and exhausting all along the ridge, the flow rate created when the
attic has nearly equal intake and exhaust openings is as follows:

where Q = stack induced flow (cfm), A = free area of inlet
openings (ft2), and [Delta]h = height difference between
inlet and exhaust openings (ft). If the inlet and outlet areas are not
about equal, a correction must be applied.
To determine the free area of inlets needed to
cool an attic enough by natural, stack-induced ventilation, equations 1
and 2 are equated. Then,

If the required inlet and outlet areas can be
provided, natural ventilation will suffice to keep the attic cool enough
to prevent icings. If the required inlet and outlet areas cannot be provided,
mechanical ventilation will also be needed.
|
 |
 |
| These two buildings were photographed at
the same time. The building shown on the left has its original venting,
and is experiencing severe icings. The building on the right with improved
attic ventilation has no icing problems at all. |
|
Recommendations
Problematic icings appear to develop very slowly,
if at all, when the outside temperature is above 22°F. We feel that
owing to variations in temperature within an attic, design should be based
on an attic temperature of 30°F. Thus we recommend that to eliminate
icing problems, attic ventilation systems be sized to maintain an attic
temperature of 30°F when the outside temperature is 22°F. We have
modified several buildings to improve attic ventilation using these guidelines.
Severe icings did not form on them last winter. Instrumentation we installed
to monitor their performance appears to validate our design approach. Properly
designed attic ventilation systems that create "cold" ventilated
roofs avoid the many problems associated with ice dams and icicles along
roof eaves.
Our research was conducted on relatively large
buildings. Other work we have done using the same design approach indicates
that icing problems on most smaller residential buildings can be solved
by providing or improving on natural ventilation (mechanical ventilation
is usually not needed). In homes it is important to insure that the natural
ventilation provided to cool the roof is not somehow blocked. Also, heating
and ventilating ducts that pass through the attic should be well sealed
and insulated and the heat they add to the attic should be considered when
sizing the ventilation system. Finally, good insulation and continuous
air barriers between the living space and the attic are essential so as
to minimize the passage of heat and warm air into the attic (see "Beauty
and the Beast Upstairs," p. 27). In cold regions, vapor retarders
are often necessary to reduce moisture migration. The ventilation provided
to minimize icings also serves as a second line of defense against accumulation
of moisture in attics.
Wayne Tobiasson and James Buska are research
civil engineers, and Alan Greatorex is a civil engineering technician with
the U.S. Army Corps of Engineers Cold Regions Research and Engineering
Laboratory (CRREL) in Hanover, New Hampshire.
|