Table 1. Results of Reflective Roof Retrofit Field Tests
Energy use (kWh/day) Reduction in utility
Test Site and Description Albedo before Albedo after Before After Savings coincident peak demand (5-6 pm)
________________________________________________________________________________________________________________________________
Site #0 Merritt Island -- 0.22 0.73 38.7 34.7 4.0 Not Measured
white ceramic coating on asphalt (11%)
shingles, concrete block with R-25
ceiling insulation, attic duct system
________________________________________________________________________________________________________________________________
Site #1 Cocoa Beach -- 0.21 0.73 40.6 30.3 10.3 661 W
white elastomeric coating on asphalt (25%) (28%)
shingles and flat gravel, R-11
attic insulation, attic duct system
________________________________________________________________________________________________________________________________
Site #2 Cocoa Beach -- 0.20 0.73 35.5 20.1 15.4 858 W
white elastomeric coating on tar paper; (43%) (38%)
flat roof and no attic insulation,
attic duct system
________________________________________________________________________________________________________________________________
Site #3 West Florida -- 0.08 0.61 22.4 16.8 5.6 496 W
white elastomeric coating on asphalt (25%) (30%)
shingles, no attic insulation,
no attic duct system
________________________________________________________________________________________________________________________________
Site #4 Miami -- 0.31 0.61 51.9 43.9 8.0 444 W
white coating for gravel roof, R-11 (15%) (16%)
attic insulation, attic duct system
________________________________________________________________________________________________________________________________
Site #5 Merritt Island -- 0.20 0.64 57.5 45.9 11.6 988 W
white elastomeric coating on tile roof, (20%) (23%)
R-7 attic insulation, attic duct system
________________________________________________________________________________________________________________________________
Averages 0.20 0.68 41.1 31.5 9.2 683 W
(23%) (27%)