Procedure:
1. Measure building, calculate area and volume.
Not needed for CFM, only for ACH and Leakage Ratio.
2. Measure temperature inside and out.
3. Shut off combustion appliances.
Customers burning wood or coal need prior notification.
Close fireplace damper, cover ashes if damper not tight.
4. Verify condition of intentional openings.
Doors and windows closed, interior doors open.
Seal mechanical ventilation, clothes dryer if desired.
Fill plumbing traps if house not occupied.
5. Decide on configuration of doors to semi-conditioned
spaces.
In general, include partially heated spaces.
When in doubt, test both ways.
6. Set up blower door.
Follow manufacturer's instructions.
When possible, use doorway directly to outside.
If not, make sure end of tubing is all the way outside.
7. Zero the gauges.
Follow manufacturer's instructions.
8. Take measurements.
Try for at least 5 readings at equal intervals from 10 to 60 Pa.
If gauges move too much, use multiple outside ports, wind dampers.
Correlation coefficient should be at least .98, preferably .99.
Generate enough info (CFM50) on site to get idea of leakiness.
9. Look for leaks
20-30 Pa depressurization, depending upon temperature outside.
Focus on:
Areas that experience higher pressures (top and bottom).
Areas where moisture escapes (upper stories, humid rooms).
Areas where pipes freeze.
Areas with specific comfort problems (cold drafts).
Problems that are cheap (quick) to fix.
Rough holes, often not accessible from living space.
Compartmentalize--check individual rooms by cracking open door.
10. If heated by combustion equipment, perform combustion safety tests.
11. If heated by a furnace, perform MAD-AIR tests (see " Air Handler Fan: A
Driving Force for Air Infiltration," HE Nov/Dec '89, p.13).
12. Turn combustion appliances back on (check pilot lights).
Remove temporary seals, if used.