Table 1. Summary of Total Duct Leakage Flows
Data for 28 houses obtained using two methods specified by the American Society
for Testing and Materials--the "blower door" method and the "flow hood" method.
Note: Negative pressures are impossible and indicate computational errors.
Total duct leakage
(cubic feet per minute
at 25 pascals) Average Median Minimum Maximum
_______________________________________________________________
PRESSURIZATION
Blower door method 240 200 -40 600
_______________________________________________________
Flow hood method 250 210 90 480
_______________________________________________________________
DEPRESSURIZATION
Blower door method 220 230 -10 450
_______________________________________________________
Flow hood method 250 200 110 600