Leakage tests Measured
(House pressurized to 50 Pascals) Fresh Exhaust Fan
Infiltration Duct leakage Air Supply Air Flow
Damper (air changes (cubic feet (cubic feet (cubic feet
House Type per hour) per minute) per miute) per minute)
1 Electronically 2.8 66 65 45
activated
2 Electronically 2.9 0 80 58
activated
3 Electronically 3.6 66 187 94
activated
4 Electronically 2.5 130 100 84
activated
5 Barometric 6.1 115 80 80
6 Balancing 6.7 136 53 90
damper only
7 Balancing 4.9 65 70 75
damper only
8 Barometric 10.1 140 0 55
9 Electronically 4.9 154 40 75
activated
10 Electronically 2.5 35 72 114
activated