Table 1. Tokyo Gas field test gas heat pump and water heater
specifications
MANUFACTURER
Heat Pump Sanyo Matsashita-Panasonic Mitsubishi Daikin Toshiba
Engine Kubota Kubota Yamaha Yanmar Ishikawagima-Shibaura
_________________________________________________________________________________________________________
Capacity 1 ton 2 ton 1 ton 1 ton 2 tons
Area served 1 room 3 rooms 1 room 3 rooms 2 rooms
Engine 2 cycle 2 cycle 4 cycle 4 cycle 4 cycle
Compressor
Type Rotary Rotary Rotary Rotary Rotary
Refrigerant R-22 R-22 R-22 R-22 R-22
Hot water storage 53 gal 61 gal 41 gal 69 gal 53 gal
Cooling Performance
Capacity 13,770 Btu/hr 19,444 Btu/hr 13,254 Btu/hr 13,651 Btu/hr 20,556 Btu/hr
Coeffiecient of
Performance (COP) 0.74 0.9 0.96 0.99 0.89
Supply air temperature 59 deg.F 65 deg.F 60deg.F 61 deg.F 60 deg.F
Heating Performance
Capacity 20,199 Btu/hr 38,929 Btu/hr 19,762 Btu/hr 20,556 Btu/hr 41,310 Btu/hr
Coefficient of
Performance (COP) 1.2 1.4 1.4 1.31 1.24
Supply air temperature 115deg.F 100deg.F 101deg.F 102deg.F 120deg.F
Comments Hot water One room heated Hot water Refrigerant Hot water supplied
supplied supplied heated
to indoor unit by hot water to indoor unit by engine exhaust to indoor unit
during heating; during heating; gas; 2-pipe during heating
4-pipe system 4-pipe system; system
uses gas burner
_________________________________________________________________________________________________________
Heating mode temperatures: (45deg.F outside, 70deg.F inside)
Cooling mode temperatures: (95deg.F outside, 81deg.F inside)
Source: "Experimental Results of Field Tests of Gas Engine Heat Pump for
Residential Use," December 1985, Tokyo Gas Co.
Table 2. York Gas Heat Pump Specifications
Capacity
Cooling 3 tons
Heating 53,500 Btu/hr
Coefficient of Performance1
Cooling, at ARI (95deg.F) 0.9
Heating, at ARI (47deg.F) 1.7
Engine Single cylinder, four-stroke,
reciprocating, 5 hp
Compressor Reciprocating, two-cylinder
Maintenance interval 1 year
Auxiliary heater Integral gas boiler or domestic
hot water heater
Outdoor package dimensions 36in. x 43in. x 38in. (HxLxW)
Indoor fan motor Electronically commutated
________________________________________________________________________
1. COP is based on gas input only. Averaged for 20 cities, seasonal gas
heating is 130%, and seasonal gas cooling is 100%, including cycling and
defrost losses.
Source: Gas Research Institute
Table 3. Field Test Seasonal Efficiencies of York Gas Heat Pump
Seasonal Seasonal
Typical Climate Heating Cooling
Location Winter Summer Gas COP Gas COP
_____________________________________________________
York, Penn. Average Moderate 1.34 1.00
Chicago, Ill. Cold Moderate 1.27 1.00
Wheaton, Ill. Cold Moderate 1.25 1.03
_____________________________________________________
Girard, Ohio Cold Moderate 1.16 1.16
Baltimore, Md. Mild Humid 1.20 1.07
Maplewood, N.J. Average Average 1.27 1.05
_____________________________________________________
Brooklyn, N.Y. Average Average 1.27 0.93
Phoenix, Ariz. Mild Hot, Dry 1.04 1.02
Atlanta, Ga. Mild Hot, Humid 1.54 1.21
_____________________________________________________
Salt Lake City, Utah (high altitude)
Cold Average 1.27 0.93
_____________________________________________________
Note: Seasonal COP is the heating or cooling capacity
in Btu divided by the gas heat pump gas consumption in
Btu. Maximum electric consumption is 600 W.